Skip to main content
Calcimator

Cable Ampacity Calculator

Determine cable ampacity with NEC derating factors for temperature, conduit fill, and continuous loads.

Inputs

AWG
(1=THHN, 2=XHHW)
°C
conductors
(0=no, 1=yes)

Results

Derated Ampacity

40 A

Required Breaker Size

40 A

Base Ampacity40 A
Maximum Allowable Load32 A
How to Use This Calculator
  1. Select the Conductor Size in AWG — smaller AWG numbers indicate larger wires (e.g., AWG 10 is larger than AWG 14).
  2. Select the Insulation Type: THHN is the most common general-purpose wire; XHHW is used in wet locations.
  3. Enter the Ambient Temperature in °C around the conductors — NEC base is 30°C; higher temperatures require derating.
  4. Enter the number of Current-Carrying Conductors in the raceway — three or fewer requires no fill derating.
  5. Indicate whether this is a Continuous Load (3+ hours) — NEC requires conductors to be derated to 80% for continuous loads.
  6. Read the Derated Ampacity in amperes and the Required Breaker Size to confirm the circuit is properly protected.
Ad Placeholder

Related Calculators

Ad Placeholder