Emergency Generator Calculator

Size emergency generators with altitude and temperature derating, fuel consumption, and runtime estimates.

Inputs

kW
kW
m
°C

Results

Required Generator Size

300 kW

Required KVA

375 kVA

Derated Capacity300 kW
Fuel Consumption (75% load)60.75 L/hr
Runtime (500L tank)8.2 hours
How to Use This Calculator
  1. Enter the Total Critical Load in kW — sum all loads that must remain on during a power outage.
  2. Enter the Largest Motor Starting Load in kW — motor inrush is typically 3× running kW and determines the generator's transient kVA requirement.
  3. Set the Power Factor — standard standby generators are rated at 0.8 PF.
  4. Enter the Site Altitude in meters above sea level — derating begins above 1,000 m at approximately 3.5% per 300 m.
  5. Enter the Maximum Ambient Temperature in °C — derating begins above 40°C.
  6. Read the Required Generator Size in kW and kVA, then check Fuel Consumption (L/hr) and estimated Runtime from a 500L tank to plan fuel logistics.