Size emergency generators with altitude and temperature derating, fuel consumption, and runtime estimates.

Inputs

kW
kW

NFPA 110 / IEEE Std 446: standard generator 0.8 PF rating; kW = kVA Γ— 0.8; size in kW not kVA

ft

ISO 8528-1: no derating ≀1,000 m; ~3–4% per 300 m above 1,000 m; at 2,000 m ~10–14% derating

Β°F

Results

Required Generator Size

300 kW

Required KVA

375 kVA

Derated Capacity300 kW
Fuel Consumption (75% load)60.75 L/hr
Runtime (500L tank)8.2 hours
How to Use This Calculator
  1. Enter the Total Critical Load in kW β€” sum all loads that must remain on during a power outage.
  2. Enter the Largest Motor Starting Load in kW β€” motor inrush is typically 3Γ— running kW and determines the generator's transient kVA requirement.
  3. Set the Power Factor β€” standard standby generators are rated at 0.8 PF.
  4. Enter the Site Altitude in meters above sea level β€” derating begins above 1,000 m at approximately 3.5% per 300 m.
  5. Enter the Maximum Ambient Temperature in Β°C β€” derating begins above 40Β°C.
  6. Read the Required Generator Size in kW and kVA, then check Fuel Consumption (L/hr) and estimated Runtime from a 500L tank to plan fuel logistics.