Heat Exchanger Sizing Calculator

Size a counterflow heat exchanger using the LMTD method. Calculate heat duty, log mean temperature difference, and required surface area.

Inputs

°F
°F
°F
°F
GPM
BTU/lb·°F
BTU/hr·ft²·°F

Results

Heat Duty

3,998,400 BTU/hr

Required Surface Area

340.4 ft²

LMTD78.3 °F
Effectiveness57.1%
Mass Flow Rate49,980 lb/hr
How to Use This Calculator
  1. Enter the Hot Fluid Inlet and Outlet temperatures in °F to define the hot-side duty.
  2. Enter the Cold Fluid Inlet and Outlet temperatures in °F — verify the cold outlet is lower than the hot inlet for a valid counterflow arrangement.
  3. Enter the Hot Side Flow Rate in GPM and the Specific Heat of the fluid (water = 1.0 BTU/lb·°F).
  4. Set the Overall U-Value in BTU/hr·ft²·°F: water-to-water ≈ 150–300, steam-to-water ≈ 200–500.
  5. Review the Heat Duty in BTU/hr and the LMTD in °F — the LMTD drives the required surface area.
  6. Use the Required Surface Area in ft² to select or specify a heat exchanger model from vendor catalogs.