Skip to main content
Calcimator

Corrosion Control Calculator

Calculate the Langelier Saturation Index (LSI) and Ryznar Stability Index for pipe corrosion prevention in drinking water.

Inputs

mg/L as CaCO₃
mg/L as CaCO₃
mg/L
°C

Results

Langelier Saturation Index

-1.01

LSI Interpretation

Highly Corrosive (aggressive water)

Ryznar Stability Index9.22
RSI InterpretationVery Corrosive
Aggressive Index11.1
AI InterpretationModerately Aggressive
Saturation pH (pHs)8.21
Target pH for Balance8.21
Recommended TreatmentpH adjustment (lime/caustic soda) + corrosion inhibitor
Lead/Copper Rule RiskModerate Risk
CaCO₃ Precipitation Potential-25 mg/L
How to Use This Calculator
  1. Enter Water pH from your latest distribution system or treatment plant measurement.
  2. Input Total Alkalinity (mg/L as CaCO₃) and Calcium Hardness (mg/L as CaCO₃) from a water quality analysis.
  3. Enter Total Dissolved Solids (mg/L) and Water Temperature (°C) to complete the water chemistry profile.
  4. Review the Langelier Saturation Index (LSI): negative values indicate corrosive water, positive values indicate scaling tendency.
  5. Check the Ryznar Stability Index (RSI) and Aggressive Index (AI) for additional corrosion characterization.
  6. Use the interpretation outputs to guide pH, alkalinity, or inhibitor adjustments to meet Lead and Copper Rule corrosion control requirements.