Control Valve Sizing Calculator
Cv from flow rate, pressure drop, and fluid properties.
Inputs
Results
Calculated Cv
44.72
Selected standard Cv
46
How to Use This Calculator
- Enter Design flow (GPM), Valve pressure drop (psi), and Coil/circuit drop (psi).
- Set Specific gravity, Valve Type, and Globe (50:1 rangeability).
- Adjust Ball (200:1 rangeability), Butterfly (25:1, large flows) as needed.
- Review Calculated Cv and Selected standard Cv.
- Use Oversize ratio and Valve authority (N) to inform your decision.
How the result changes with Design flow (GPM)
| Design flow (GPM) | Calculated Cv | Selected standard Cv |
|---|---|---|
| 10,000 | 4,472.14 | 1,160 |
| 35,000 | 15,652.48 | 1,160 |
| 65,000 | 29,068.88 | 1,160 |
| 90,000 | 40,249.22 | 1,160 |
What each input means
- Design flow (GPM)
- Design water flow rate through the valve in gallons per minute.
- Valve pressure drop (psi)
- Pressure drop across the control valve at design flow. Higher = better authority but more pump energy.
- Coil/circuit drop (psi)
- Pressure drop across the coil and piping circuit (excluding valve). Used for authority calculation.
- Specific gravity
- Fluid specific gravity relative to water. Water = 1.0, 30% glycol ≈ 1.04.
- Valve Type
- Select control valve type
What each result means
- Calculated Cv
- Required valve flow coefficient from the ISA sizing equation: Cv = Q × sqrt(SG / deltaP).
- Selected standard Cv
- Next available standard valve Cv size. Choose the smallest standard size >= calculated Cv.
- Oversize ratio
- Selected Cv / Calculated Cv. Should be 1.0-1.5; >2.0 indicates oversizing risk.
- Valve authority (N)
- Ratio of valve drop to total circuit drop. Target >= 0.5 for good control. < 0.3 = poor controllability.
- Authority rating (0-2)
- 0 = Poor (<0.3), 1 = Fair (0.3-0.5), 2 = Good (>=0.5).
- Valve rangeability
- Turndown ratio (max/min controllable Cv) for the selected valve type.
- Min controllable flow (GPM)
- Minimum flow the valve can control based on its rangeability.
- Port velocity (ft/s)
- Approximate fluid velocity through the valve port. Keep < 12 ft/s to avoid erosion and noise.
How this is calculated
Worked example, using the default values
- Identify Input Parameters4 parametersDesign flow (GPM) = 100, Valve pressure drop (psi) = 5, Coil/circuit drop (psi) = 5, Specific gravity = 1 = 5 input(s) provided
- Calculate Calculated CvCalculated Cv = flowGpm * sqrt(specificGravity / valveDeltaPsi)44.72 = 44.72
- Calculate Selected standard CvSelected standard Cv46 = 46
- Calculate Oversize ratio1.03 = 1.03
- Calculate Valve authority0.5 = 0.5
Engine last updated . Checked against 2 independently-derived tests — how we verify calculators.
Related Calculators
The questions that sit next to this one — chosen by subject, including calculators filed under a different category.
Damper Sizing Calculator
Damper area from CFM and velocity limits.
Hvac ControlsSetpoint Optimization Calculator
Energy savings from supply air temperature reset.
Process EngineeringControl Valve Cv Sizing Calculator
Size control valves per ISA/IEC 60534 for liquid or gas service. Calculate required Cv, check for choked flow, and select nearest standard valve size.
Fluid PowerPneumatic Valve Sizing Calculator
Calculate required valve Cv/Kv flow coefficient for pneumatic systems with sub-critical and critical (choked) flow analysis.
Hvac ControlsBAS Point Count Calculator
Building automation point count from equipment schedule.
More in Construction & Building Trades.