Skip to main content
Calcimator

Electrical Load Calculator

Calculate total electrical load by circuit type and determine the service panel size and main breaker needed.

About this calculator

Total Circuits is a plain sum of the four circuit-count inputs -- Lighting, Outlet, Appliance, and HVAC Circuits -- and is completely unaffected by any of the four watts-per-circuit inputs, since it counts circuits, not load. Outlet Circuits carries the most weight in that sum at the calculator's defaults (8 of 16 total circuits), so it moves Total Circuits more than Lighting, Appliance, or HVAC Circuits do for an equal percentage change. Total Connected Load, by contrast, is a sum of four category totals (circuits times watts per circuit for each category), and at the defaults the Appliance category is the single largest contributor at 12,000 W of the 29,000 W total -- larger than Lighting (2,400 W), Outlet (9,600 W), or HVAC (5,000 W) -- so Appliance Circuits and Watts per Appliance Circuit each move Total Connected Load more than the corresponding lighting or HVAC inputs do. NEC Demand Load applies the standard demand factor (100% of the first 10,000 W of connected load, 40% of the remainder), which is why it comes out well below Total Connected Load once the total clears 10 kW, and why Panel Size and Main Breaker are sized off that reduced demand figure rather than the raw connected load. Panel Size and Main Breaker only change at specific NEC-standard tier boundaries (100, 125, 150, 200 A, and so on), so a small change to any single circuit input often leaves them unchanged even though it does move the underlying demand amps -- only a large enough swing pushes the recommendation to the next standard size. Panel Size is chosen from a 100-400 A table and Main Breaker from a narrower 100-200 A table; at very large loads the required capacity (demand amps times the NEC's 125% continuous-load factor) can exceed either table.

Exceeds Standard Sizing (1=Yes) fires when required capacity exceeds the Panel Size table, the Main Breaker table, or both -- but because the breaker table's ceiling (200 A) is narrower than the panel table's (400 A), there is a real range of loads (required capacity above 200 A but at or below 400 A) where the flag fires from the breaker table alone while the displayed Panel Size is still a genuinely valid, correctly-sized recommendation. Before discarding both numbers, check which one actually hit its table's ceiling -- e.g. Main Breaker reading exactly 200 A while Panel Size sits comfortably below 400 A means only the breaker needs a custom size; Panel Size itself is fine as shown. Only when Panel Size is also pinned at 400 A (or the underlying required capacity exceeds it) is the panel recommendation itself invalid. This tool applies the general demand-factor method from Article 220 of NFPA 70, the National Electrical Code (NEC) -- the first 10 kW of connected load at 100% and the remainder at 40% -- plus the NEC's 125% continuous-load factor for the panel and breaker sizing step; it does not substitute for a full NEC Article 220 load calculation with your local utility and inspector.

Inputs

W
W
W
W

Results

Total Connected Load

29,000 W

≈ 4 EV chargers

Total Amps (240V)120.8 A
NEC Demand Load17,600 W
Demand Amps (240V)73.3 A
Panel Size100 A
Main Breaker100 A
Total Circuits16
Exceeds Standard Sizing (1=Yes)0

Figures current as of 2023. Source: NFPA 70, National Electrical Code (NEC), 2023 edition, Article 220

How to Use This Calculator
  1. Enter the number of Lighting Circuits and Watts per Lighting Circuit.
  2. Add Outlet Circuits and Watts per Outlet Circuit.
  3. Enter Appliance Circuits and Watts per Appliance Circuit.
  4. Add HVAC Circuits and their wattage.
  5. Review the Total Load (amps) to size the service panel or subpanel required.
  6. If Exceeds Standard Sizing (1=Yes) is flagged, it means the Panel Size table, the Main Breaker table, or both were exceeded — check whether Main Breaker is pinned at exactly 200 A while Panel Size is well below 400 A (only the breaker needs custom sizing) versus Panel Size itself pinned at 400 A (that number is undersized too); consult an electrician for whichever value(s) actually hit their table's ceiling.

How the result changes with Appliance Circuits

Appliance CircuitsTotal Connected Load
1.523,000 W
2.2526,000 W
4.535,000 W
7.547,000 W

What each input means

Lighting Circuits
Number of dedicated lighting circuits.
Watts per Lighting Circuit
Average wattage per lighting circuit.
Outlet Circuits
Number of general-purpose outlet circuits.
Watts per Outlet Circuit
Average wattage per outlet circuit.
Appliance Circuits
Number of dedicated appliance circuits (oven, dryer, etc.).
Watts per Appliance Circuit
Average wattage per appliance circuit.
HVAC Circuits
Number of HVAC or heat pump circuits.
Watts per HVAC Circuit
Wattage per HVAC unit.

How this is calculated

Worked example, using the default values

  1. Identify Input Parameters
    4 parameters
    Lighting Circuits = 4, Watts per Lighting Circuit = 600, Outlet Circuits = 8, Watts per Outlet Circuit = 1200 = 8 input(s) provided
  2. Calculate Total Connected Load
    Total Connected Load
    29000 = 29000
  3. Calculate Total Amps
    Total Amps
    120.8 = 120.8
  4. Calculate NEC Demand Load
    NEC Demand Load
    17600 = 17600

Figures and sources

Engine last updated . Checked against 1 independently-derived test — how we verify calculators. Built by Paul Gunder, a software engineer, not a licensed financial, medical, or legal professional.

Frequently Asked Questions

Do the watts-per-circuit inputs affect Total Circuits?

No -- Total Circuits is a plain count of Lighting, Outlet, Appliance, and HVAC Circuits and never references any of the four watts-per-circuit inputs. Those wattage inputs only affect Total Connected Load and everything derived from it (demand load, demand amps, panel size, and main breaker).

Which circuit type contributes the most to my connected load by default?

Appliance circuits, at 12,000 W of the 29,000 W default total -- more than Outlet (9,600 W), HVAC (5,000 W), or Lighting (2,400 W). That is because the default appliance wattage per circuit (4,000 W, covering things like an oven or dryer) is much higher than lighting or general outlet wattage.

Why is my NEC Demand Load lower than my Total Connected Load?

The NEC demand factor this calculator applies counts the first 10,000 W of connected load at full value, then only 40% of everything above that. At the default 29,000 W total, that works out to a 17,600 W demand load -- the assumption being that not every circuit draws its full rated load simultaneously.

Why didn't my recommended panel size change when I added one more circuit?

Panel Size and Main Breaker only step up at specific NEC-standard amperage tiers (100, 125, 150, 200 A, and so on). A single added circuit does raise the underlying demand amps, but unless that increase is enough to cross the next tier boundary, the recommended panel size stays exactly where it was.

What happens if my load is too large for the panel and breaker tables?

Check Exceeds Standard Sizing (1=Yes) -- it fires when the required capacity (demand amps × 1.25) exceeds the Panel Size table (tops out at 400 A), the Main Breaker table (tops out at 200 A, a narrower ceiling), or both. Because the breaker table caps out lower, the flag can read 1 purely from the breaker side while Panel Size is still a valid, correctly-sized recommendation -- look at whether Main Breaker is pinned at exactly 200 A while Panel Size sits below 400 A; if so, only the breaker needs custom sizing. Only when Panel Size itself is pinned at 400 A (or exceeded) is that number also undersized. A load that outgrows a table entirely needs custom-sized service equipment designed with an electrician.

The questions that sit next to this one — chosen by subject, including calculators filed under a different category.

More in Construction & Building Trades.