HRV Sizing Calculator
Size heat recovery ventilators based on building volume, air change requirements, and climate conditions.
About this calculator
This calculator sizes a heat recovery ventilator (HRV) by computing required ventilation two different ways and taking whichever is larger. Method 1 scales with Building Volume and Air Changes per Hour (Building Volume x Air Changes ÷ 60); Method 2 is a simplified stand-in for ASHRAE 62.2's residential whole-building ventilation formula, which combines a per-occupant rate (7.5 CFM per person, used directly here) with a smaller area-based term keyed to conditioned floor area and bedroom count -- this calculator approximates that area term from Building Volume rather than asking for floor area and bedroom count directly, so treat Method 2's result as an ASHRAE-62.2-style estimate, not a code-compliance calculation. Method 2 scales with Occupants. At the default inputs (16,000 cu ft, 0.35 ACH, 4 occupants), the volume-based method wins at 93 CFM versus the occupant-based method's 50 CFM, so Building Volume and Air Changes per Hour drive Required Ventilation in that regime -- Occupants has no effect until it's raised enough to flip which method is larger; at 50 occupants (same building volume), the occupant-based method takes over and Required Ventilation jumps to 395 CFM. Recommended HRV Size is picked from a stepped list of standard unit sizes (70, 100, 150, 200, 250, 300, 400 CFM) rather than a continuous value, so it only changes when Required Ventilation crosses one of those thresholds -- a 10% increase in Building Volume from the default is enough to push Required Ventilation from 93 to about 103 CFM, crossing the 100 CFM boundary and bumping Recommended HRV Size from 100 to 150.
Heat Recovered and Est. Annual Savings depend on the temperature difference between Indoor and Design Outdoor Temp along with Sensible Efficiency, independent of which sizing method is active. Recommended HRV Size tops out at the largest standard unit, 400 CFM; if Required Ventilation exceeds that (very large buildings or high occupant counts), Exceeds Standard Sizing (1=Yes) flags it -- the displayed 400 CFM is only the largest table entry for reference, not a safe recommendation, and the project needs multiple units or a custom-sized commercial ERV/HRV designed with a mechanical engineer. This is a preliminary sizing estimate, not a full ASHRAE 62.2 compliance calculation or a substitute for a mechanical engineer's ventilation design.
Inputs
ASHRAE 62.2: residential 0.35 ACH target; commercial per 62.1 Table 6.2.2.1; new tight homes 0.1–0.3 ACH natural
Results
Required Ventilation
93 CFM
Recommended HRV Size
100 CFM
Figures current as of 2022. Source: ASHRAE Standard 62.2-2022, Ventilation and Acceptable Indoor Air Quality in Low-Rise Residential Buildings, whole-building mechanical ventilation rate (occupant-based + floor-area-based components)
How to Use This Calculator
- Enter Building Volume, Air Changes per Hour, and Occupants.
- Set Design Outdoor Temp, Indoor Temperature, and Sensible Efficiency.
- Review Required Ventilation (CFM) and Recommended HRV Size (CFM).
- Use Heat Recovered (BTU/hr) and Est. Annual Savings ($) to inform your decision.
- If Exceeds Standard Sizing (1=Yes) is flagged, the displayed Recommended HRV Size is undersized for your load — consult a mechanical engineer for multiple units or custom-sized equipment instead of using that number.
How the result changes with Building Volume
| Building Volume | Required Ventilation | Recommended HRV Size |
|---|---|---|
| 8,000 | 47 CFM | 70 CFM |
| 12,000 | 70 CFM | 70 CFM |
| 24,000 | 140 CFM | 150 CFM |
| 40,000 | 233 CFM | 250 CFM |
What each input means
- Building Volume
- Total interior volume of the building (floor area × ceiling height).
- Air Changes per Hour
- Target air changes per hour per ASHRAE 62.2-2022 (residential). ASHRAE 62.2 requires max(0.01×CFA + 7.5×(Nbr+1), ~15 CFM/person); typical houses 0.35 ACH. Also: minimum 7.5 CFM/person per ASHRAE 62.1 for commercial.
- Occupants
- Number of occupants for per-person ventilation requirement.
- Design Outdoor Temp
- Winter design outdoor temperature for your location. Used for heat recovery calculation.
- Indoor Temperature
- Target indoor air temperature.
- Sensible Efficiency
- Sensible heat recovery efficiency of the HRV unit. Typical range: 65–85%.
How this is calculated
Worked example, using the default values
- Identify Input Parameters4 parametersBuilding Volume = 16000, Air Changes per Hour = 0.35, Occupants = 4, Design Outdoor Temp = 10 = 6 input(s) provided
- Calculate Required VentilationRequired Ventilation93 = 93
- Calculate Recommended HRV SizeRecommended HRV Size100 = 100
- Calculate Heat RecoveredHeat Recovered4536 = 4536
- Calculate Est. Annual SavingsEst. Annual Savings272 = $272
Figures and sources
- ASHRAE 62.2 residential ventilation rate (occupant + area formula) (2022) — ASHRAE Standard 62.2-2022, Ventilation and Acceptable Indoor Air Quality in Low-Rise Residential Buildings, whole-building mechanical ventilation rate (occupant-based + floor-area-based components)
Engine last updated . Checked against 3 independently-derived tests — how we verify calculators. Built by Paul Gunder, a software engineer, not a licensed financial, medical, or legal professional.
Frequently Asked Questions
Does the calculator size for air changes or for occupants?
Whichever produces the larger required airflow -- Required Ventilation is the greater of a volume-and-air-changes-based estimate and an occupant-based ASHRAE 62.2-style estimate. At the default inputs the volume-based figure (93 CFM) wins over the occupant- based figure (50 CFM), but raising occupancy enough (to 50 occupants at the same building volume) flips it, pushing Required Ventilation to 395 CFM.
Why did a small change to building volume jump the recommended HRV size a whole tier?
Recommended HRV Size is picked from a fixed list of standard unit sizes (70, 100, 150, 200, 250, 300, 400 CFM), so it only moves when Required Ventilation crosses one of those thresholds. A 10% increase in Building Volume from the default pushes Required Ventilation from 93 to about 103 CFM, crossing the 100 CFM boundary and bumping the recommended size from 100 to 150.
Does raising the occupant count always increase the required ventilation?
Only once the occupant-based estimate becomes the larger of the two sizing methods. At the default building volume and air-change rate, Occupants has no effect on Required Ventilation because the volume-based estimate already exceeds it; raising Occupants high enough for the occupant-based estimate to overtake the volume-based one is what makes it start moving the result.
What determines the estimated annual energy savings?
Est. Annual Savings comes from Heat Recovered, which depends on Required Ventilation, the temperature difference between Indoor Temperature and Design Outdoor Temp, and Sensible Efficiency -- a colder design outdoor temperature or a higher-efficiency unit both increase the heat recovered and therefore the estimated savings, independent of which sizing method set the airflow.
What if my required ventilation is larger than the biggest standard HRV unit?
Check Exceeds Standard Sizing (1=Yes). Recommended HRV Size tops out at 400 CFM; if Required Ventilation is larger than that -- for example, a large building volume or a high occupant count -- this flag reads 1 and the displayed 400 CFM is just the largest standard size shown for reference, not a real recommendation. A load that large needs multiple HRV units or a custom-sized commercial ERV/HRV designed with a mechanical engineer.
Related Calculators
The questions that sit next to this one — chosen by subject, including calculators filed under a different category.
Ventilation Rate Calculator
Calculate required outdoor air ventilation rates per ASHRAE Standard 62.1 based on occupancy and space type.
HVACManual J Heat Load Calculator
Estimate heating and cooling loads using a simplified Manual J method based on building envelope, windows, and occupancy.
Biomedical EngineeringVentilator Settings Calculator
Calculate initial ventilator parameters including ideal body weight, tidal volume, respiratory rate, minute ventilation, PEEP, and FiO₂.
WearablesHealth Metric Dashboard Calculator
Compute a composite readiness score from wearable health metrics: resting HR, HRV, sleep duration, daily steps, SpO2, and stress level.
Air QualityAir Change Rate Calculator
Calculate air changes per hour (ACH) from airflow rate and room volume with recommendations by room type.
More in Construction & Building Trades.