Motor Circuit Calculator
Branch circuit protection, conductor, and starter sizing from motor HP per NEC Article 430.
About this calculator
This calculator looks up a motor's full-load amperage (FLA) from Table 430.248 (single-phase) or 430.250 (three-phase) in the National Electrical Code, NFPA 70 (NEC), then derives every other result from that one figure: Max OCPD size at 250% of FLA for a standard inverse-time breaker or 175% for a dual-element fuse (NEC 430.52), Min conductor ampacity at 125% of FLA (NEC 430.22), and Overload relay trip at 115% (NEC 430.32). Motor horsepower and Voltage both feed the FLA lookup, and Motor horsepower now moves Motor FLA (amps) further than an equivalent percentage change to Voltage does -- at the default inputs, a 10% increase in Motor horsepower (10 to 11 HP) moves Motor FLA by 50%, roughly four to five times the ~9-11% swing from an equivalent 10% change to Voltage, because horsepower selects between sparse NEC table entries (each in-between value rounding up to the next standard size) while Voltage scaling is a smooth, continuous ratio. Raising Voltage still lowers Motor FLA (amps) for the same horsepower, since the same power delivered at higher voltage draws less current. Protection type only affects Max OCPD size, choosing between the 250% breaker multiplier and the 175% fuse multiplier -- it has no effect on Motor FLA (amps) itself, which is set entirely by horsepower, phase, and voltage.
For horsepower values that fall between the NEC table's standard listed sizes, the calculator rounds up to the next larger listed horsepower rather than interpolating or estimating -- so an in-between horsepower value always gets the FLA (and every downstream breaker, conductor, and overload figure) of the next standard motor size up, never a smaller or intermediate one. That protects against under-sizing within the tables' real coverage range, but the breaker and conductor tables are finite: once required OCPD or conductor ampacity exceeds their largest listed entry, the loop has nowhere left to round up to. Exceeds Standard Sizing (1=Yes) flags that condition -- for a 460V three-phase motor on a standard inverse-time breaker this first happens just above 250 HP (verified: a 300 HP motor needs 451A of conductor ampacity, but the largest listed conductor, 500 kcmil, is only rated for 380A), and it can trigger at much lower horsepower for single-phase motors, whose FLA table only lists sizes up to 10 HP before falling back to a linear extrapolation (verified: a 230V single-phase motor trips the flag above roughly 38.5 HP). When the flag reads 1, the displayed conductor and breaker figures are only the largest table entries shown for reference -- not a safe recommendation -- and the circuit needs a custom or paralleled-conductor design from an electrical engineer.
Inputs
Results
Motor FLA (amps)
14
Figures current as of 2026. Source: National Fire Protection Association, NFPA 70, National Electrical Code (NEC), 2026 Edition
How to Use This Calculator
- Enter the motor nameplate horsepower rating.
- Select single-phase (1) or three-phase (3) and the supply voltage (230 V single-phase or 460 V three-phase are common).
- Choose the protection type: inverse-time breaker (1) at 250% FLA or dual-element fuse (2) at 175% FLA per NEC 430.52.
- Read the full-load amperage (FLA) from NEC Table 430.248/250, the maximum overcurrent device size, and the minimum conductor ampacity at 125% of FLA.
- Use the overload relay trip amperage to set the thermal overload in the motor starter.
- If Exceeds Standard Sizing (1=Yes) is flagged, the displayed breaker and conductor figures are only the largest standard table entries, not a safe recommendation for this load -- consult an electrical engineer for a custom or paralleled-conductor design instead.
How the result changes with Motor horsepower (HP)
| Motor horsepower (HP) | Motor FLA (amps) |
|---|---|
| 5 | 7.6 |
| 7.5 | 11 |
| 15 | 21 |
| 25 | 34 |
What each input means
- Motor horsepower (HP)
- Nameplate motor horsepower rating.
- Phase (1 or 3)
- Single-phase (1) or three-phase (3) motor.
- Voltage (V)
- Supply voltage. Common: 230V single-phase, 460V three-phase.
- Protection type
- 1 = Inverse-time breaker (250% FLA), 2 = Dual-element fuse (175% FLA) per NEC 430.52.
What each result means
- Motor FLA (amps)
- Full-load amperage from NEC Table 430.248/250.
- Max OCPD size (amps)
- Maximum overcurrent protective device rating per NEC 430.52.
- Min conductor ampacity (A)
- 125% of FLA per NEC 430.22.
- Selected conductor ampacity (A)
- Ampacity of selected conductor at 75°C (THWN-2).
- Overload relay trip (A)
- Overload relay set at 115% of FLA per NEC 430.32.
- Conductor size (AWG)
- Selected conductor wire gauge at 75°C (THWN-2) ampacity, per NEC Table 310.16.
- Exceeds Standard Sizing (1=Yes)
- 1 if the required OCPD or conductor ampacity exceeds the largest entry in the standard breaker (800A) or conductor (500 kcmil / 380A) table -- the displayed breaker/conductor figures are only the largest table entries, NOT a safe recommendation for this load. Consult an electrical engineer for a custom or paralleled-conductor design.
How this is calculated
Worked example, using the default values
- Identify Input Parameters4 parametersMotor horsepower (HP) = 10, Phase (1 or 3) = 3, Voltage (V) = 460, Protection type = 1 = 4 input(s) provided
- Calculate Motor FLA14 = 14
- Calculate Max OCPD sizeMax OCPD size35 = 35
- Calculate Min conductor ampacityMin conductor ampacity = fla * 1.2517.5 = 17.5
Figures and sources
- Motor FLA tables (430.248, 430.250) and OCPD/conductor/overload multipliers (430.52, 430.22, 430.32) (2026) — National Fire Protection Association, NFPA 70, National Electrical Code (NEC), 2026 Edition
Engine last updated . Checked against 1 independently-derived test — how we verify calculators. Built by Paul Gunder, a software engineer, not a licensed financial, medical, or legal professional.
Frequently Asked Questions
Does Protection type change the full-load amperage shown?
No -- Motor FLA (amps) is looked up from horsepower, phase, and voltage alone. Protection type only changes Max OCPD size, switching between a 250% multiplier for a standard inverse-time breaker and a 175% multiplier for a dual-element fuse per NEC 430.52.
Why does raising the voltage lower the full-load amperage?
A motor delivering the same horsepower at a higher voltage draws less current, so Motor FLA (amps) scales down as Voltage rises -- the calculator applies this by scaling the NEC table's reference-voltage FLA figure by the ratio of that reference voltage to your entered Voltage.
Which matters more for full-load amperage: horsepower or voltage?
Motor horsepower, at this calculator's default settings -- because the NEC FLA tables only list sparse standard sizes, an in-between horsepower value jumps to the next listed tier rather than scaling smoothly, so a 10% increase in Motor horsepower (10 to 11 HP) moves Motor FLA (amps) by 50%, roughly four to five times the ~9-11% swing from an equivalent 10% change to Voltage, which scales FLA by a smooth, continuous ratio instead.
Are results accurate for horsepower values not listed in the NEC tables?
Within the tables' real coverage range, yes, and conservatively so -- NFPA 70 (NEC) Tables 430.248 and 430.250 list FLA at specific standard horsepower sizes, and for a horsepower value that falls between listed sizes, this calculator rounds up to the next larger listed horsepower rather than interpolating or estimating, so the breaker, conductor, and overload figures shown are always sized for at least as large a motor as you entered. But the breaker and conductor tables themselves are finite: once required OCPD or conductor ampacity exceeds their largest entry -- for a 460V three-phase motor on a standard breaker, that starts just above 250 HP -- there's no larger entry left to round up to, and the displayed figures stop being a safe recommendation. Check Exceeds Standard Sizing (1=Yes): if it reads 1, consult an electrical engineer for a custom or paralleled-conductor design instead of using the numbers shown.
What if required OCPD or conductor ampacity is larger than the biggest standard entry?
Check Exceeds Standard Sizing (1=Yes). Max OCPD size tops out at 800A and Min conductor ampacity tops out at 380A (500 kcmil); if the motor's required OCPD or conductor ampacity is larger than that -- verified starting just above 250 HP for a 460V three-phase motor on a standard breaker, and around 38.5 HP for a 230V single-phase motor -- this flag reads 1 and the displayed breaker/conductor figures are only the largest standard table entries shown for reference, not a real recommendation. A load that large needs a custom or paralleled-conductor circuit designed by an electrical engineer.
Related Calculators
The questions that sit next to this one — chosen by subject, including calculators filed under a different category.
Electrical Panel Schedule Calculator
Panel load calculation with NEC demand factors for lighting, receptacles, motors, and HVAC.
Construction ElectricalData Cable Calculator
Cable runs, conduit fill per NEC Table 1, and pathway sizing from network drop count.
Electrical & PlumbingCircuit Breaker Calculator
Calculate the required breaker amperage and wire gauge for your electrical load with NEC compliance checking.
Pool ConstructionPool Electrical Calculator
Circuit requirements for pump, heater, lights, and automation.
Home Automation & Smart HomeEV Charger Circuit Calculator
Size the electrical circuit for a Level 2 EV charger: breaker, wire gauge, daily energy needs, and charging costs.
More in Construction & Building Trades.