Size HEPA air scrubbers for restoration by calculating required CFM and unit count based on room volume and air changes.

About this calculator

Sizing air scrubbers for a mold remediation, fire restoration, or other contaminated work area comes down to one core relationship: required airflow, in cubic feet per minute (CFM), equals the room's volume multiplied by how many times per hour you need to fully exchange its air, divided by 60 to convert hours to minutes. ANSI/IICRC S520 specifies 4 air changes per hour (ACH) as its minimum within containment for general remediation -- that's the one number the standard itself sets. 6 or more ACH shows up widely in restoration trade and vendor guidance as a step up for more aggressive active remediation where contaminant load is higher, but it isn't itself a second S520-specified figure the way the 4 ACH minimum is.

This calculator applies the CFM formula to your Room Volume and Target Air Changes/Hour, then divides the required CFM by a standard single-unit nameplate capacity of 500 CFM -- derated to roughly 70% (about 350 CFM delivered) to account for the airflow a loaded HEPA/prefilter stack and containment ductwork actually deliver versus a clean, unloaded unit's rated capacity -- and rounds up, since a fraction of a unit isn't installable. Filter Type affects how often you'll need to change filters, not the airflow sizing itself — a HEPA filter capturing particulates typically lasts longer between changes than a carbon filter working continuously to adsorb VOCs and odors, and a combination HEPA-plus-carbon filter tends to need the most frequent changes since it's handling both contaminant types at once. These filter-life figures are representative planning baselines by media type only; they don't adjust for how contaminated the air actually is, room size, target ACH, or unit duty cycle, all of which affect real-world filter life.

Inputs

Results

CFM Required

400 CFM

Air Scrubbers Needed

2

Filter Life31.3 days

Figures current as of 2024. Source: Institute of Inspection, Cleaning and Restoration Certification (IICRC), ANSI/IICRC S520, Standard for Professional Mold Remediation, 4th Edition (2024)

How to Use This Calculator
  1. Enter the room volume (cu ft) (length x width x height) for the work area.
  2. Set the target air changes per hour (ACPH) -- ANSI/IICRC S520 specifies a 4 ACH minimum within containment; 6+ ACH is common trade practice for more aggressive active remediation.
  3. Select the filter type: HEPA (particles), Carbon (VOCs/odor), or Combo HEPA + carbon.
  4. Review the required CFM and number of air scrubbers needed for the space -- unit count already includes a derate for real-world filter loading, not just the bare nameplate rating.
  5. Check filter life (days) to plan filter changeout schedules and consumables budget.

How the result changes with Room Volume (cu ft)

Room Volume (cu ft)CFM RequiredAir Scrubbers Needed
2,000200 CFM1
3,000300 CFM1
6,000600 CFM2
10,0001,000 CFM3

What each input means

Room Volume (cu ft)
Total volume of the space (sqft × ceiling height)
Target Air Changes/Hour
Desired air changes per hour — 4 ACH for maintenance, 6+ for active remediation
Filter Type
HEPA captures particulates and generally lasts longest between changes; Carbon adsorbs VOCs/odors and loads faster; Combo handles both but needs the most frequent changes.

How this is calculated

Worked example, using the default values

  1. Identify Input Parameters
    3 parameters
    Room Volume (cu ft) = 4000, Target Air Changes/Hour = 6, Filter Type = 1 = 3 input(s) provided
  2. Calculate CFM Required
    CFM Required = (Room Volume × Target ACH) ÷ 60
    (4000 × 6) ÷ 60 = 400 CFM = 400 CFM
  3. Calculate Air Scrubbers Needed
    Units Needed = ceil(CFM Required ÷ (500 CFM nameplate × 0.7 loaded-filter derate))
    ceil(400 ÷ 350) = 2 = 2 unit(s)
  4. Calculate Filter Life
    Filter Life = Filter Media Baseline Hours ÷ 24 (running 24/7)
    750 hrs ÷ 24 = 31.3 days = 31.3 days

Figures and sources

Engine last updated . Checked against 3 independently-derived tests — how we verify calculators. Built by Paul Gunder, a software engineer, not a licensed financial, medical, or legal professional.

Frequently Asked Questions

Why does Filter Type change the filter life estimate but not the CFM Required or unit count?

CFM Required and unit count depend entirely on Room Volume and Target Air Changes/Hour, since those two figures determine how much air needs to move through the space regardless of what kind of filter medium is doing the filtering. Filter Type only changes how quickly the filter media itself becomes loaded and needs replacement — HEPA media handles particulates differently than carbon media handles gaseous VOCs and odors, so their typical service-life hours differ even when both are installed in units delivering identical airflow. These filter-life hours are representative planning baselines for each media type; they don't adjust for how contaminated the air actually is, how large the space is, or how many units are running, all of which affect how fast a filter actually loads in the field — treat the estimate as a starting point for budgeting replacement filters, not an exact schedule.

Where does the 6 ACH target for active remediation come from?

ANSI/IICRC S520 specifies 4 air changes per hour as the minimum within containment for general remediation — that's the one figure the standard itself sets. 6 or more ACH shows up widely in restoration trade and vendor guidance as a step up for more aggressive active remediation (heavier contaminant load, active demolition), but it isn't itself an S520-mandated number the way the 4 ACH minimum is. Treat 4 ACH as the standard's floor and 6+ ACH as common industry practice above that floor, not as a second IICRC-specified figure.

What happens if I round Room Volume down because part of my space has a lower ceiling?

Since CFM Required scales directly with the volume you enter, underestimating volume by ignoring a taller section of ceiling will undersize your air-changes-per-hour rate for the space you're actually treating — you'll get fewer real air changes per hour than the number you set as your target. Calculate volume as square footage times the true average ceiling height for irregular spaces, or split a space with very different ceiling heights into sections and size each one separately for an accurate result.

Is 500 CFM per unit a fixed assumption, or does it vary by the actual equipment I rent or own?

500 CFM is used here as a representative nameplate capacity for a standard commercial HEPA air scrubber, but real units on the market commonly range from around 500 up to 2,000 CFM depending on model and size, so a job renting larger units could need fewer of them than this calculator's unit count suggests. This calculator also derates that nameplate figure to about 70% (roughly 350 CFM delivered per unit) to account for real-world airflow loss from filter loading and containment leakage rather than assuming a brand-new, unloaded unit performs at full nameplate CFM throughout the job. Check your actual equipment's rated CFM and derate it similarly if your units differ meaningfully from the 500 CFM assumption used here.