Chiller Sizing Calculator
Size chiller systems based on water flow rate, temperature differential, diversity factor, and efficiency metrics.
Inputs
Rule of thumb: 2.4 GPM/ton at 10°F ΔT; 3.0 GPM/ton at 8°F ΔT per ASHRAE
Standard CHWR: 54°F (high ΔT systems use 58–60°F for energy savings)
Standard CHWS: 44°F; high-efficiency: 46–48°F; humidity control requires ≤45°F
Results
Required Cooling Capacity
194.79 tons
≈ 33 elephants
Estimated Chiller Power
155.83 kW
≈ 10 homes' peak draw
How to Use This Calculator
- Enter Chilled Water Flow, Entering Water Temp, and Leaving Water Temp.
- Set Diversity Factor and Safety Factor.
- Review Required Cooling Capacity (tons) and Estimated Chiller Power (kW).
- Use Cooling Capacity (BTU/hr) and Power per Ton (kW/ton) to inform your decision.
How the result changes with Entering Water Temp
| Entering Water Temp | Required Cooling Capacity | Estimated Chiller Power |
|---|---|---|
| 46 | 38.96 tons | 31.17 kW |
| 61 | 331.15 tons | 264.92 kW |
| 79 | 681.77 tons | 545.42 kW |
| 94 | 973.96 tons | 779.17 kW |
What each input means
- Chilled Water Flow
- Chilled water flow rate through the evaporator in gallons per minute. ASHRAE 90.1 and AHRI 550/590 govern chiller performance ratings at standard conditions.
- Entering Water Temp
- Temperature of chilled water returning to the chiller (after absorbing heat). ASHRAE 90.1 standard chilled water design is 44°F supply / 54°F return (10°F ΔT).
- Leaving Water Temp
- Temperature of chilled water leaving the chiller (supply to building). Standard ASHRAE 90.1 design is 44°F supply; higher supply temps (46–48°F) improve efficiency (COP) but reduce dehumidification.
- Diversity Factor
- Percentage of total load expected to occur simultaneously. Accounts for partial loading.
- Safety Factor
- Oversizing factor for future expansion or extreme conditions. 110% = 10% safety margin.
How this is calculated
Worked example, using the default values
- Identify Input Parameters4 parametersChilled Water Flow = 500, Entering Water Temp = 54, Leaving Water Temp = 44, Diversity Factor = 85 = 5 input(s) provided
- Calculate Required Cooling CapacityRequired Cooling Capacity194.79 = 194.79
- Calculate Estimated Chiller PowerEstimated Chiller Power155.83 = 155.83
- Calculate Cooling CapacityCooling Capacity2337500 = 2337500
- Calculate Power per TonPower per Ton0.8 = 0.8
Engine last updated . Checked against 2 independently-derived tests — how we verify calculators.
Related Calculators
The questions that sit next to this one — chosen by subject, including calculators filed under a different category.
Economizer Savings Calculator
Estimate energy and cost savings from an HVAC economizer by comparing mechanical cooling hours to free-cooling hours.
HVACCoil Selection Calculator
Calculate sensible, latent, and total cooling capacity of HVAC coils with sensible heat ratio from air-side measurements.
Data CenterCooling Capacity Calculator
Calculate cooling requirements from IT load, PUE, and airflow parameters for data center HVAC design.
HVACBTU Calculator
Calculate heating and cooling BTU requirements for your room or home. Determine the right AC tonnage and furnace size based on room dimensions, insulation, and climate.
More in Construction & Building Trades.