Coil Selection Calculator
Calculate sensible, latent, and total cooling capacity of HVAC coils with sensible heat ratio from air-side measurements.
About this calculator
This calculator estimates a cooling coil's sensible, latent, and total capacity from airflow and entering/leaving air temperatures. Sensible Capacity comes from the dry-bulb temperature drop (1.08 x CFM x change in dry-bulb temperature), which is the standard sensible-heat formula for air at sea-level density. Total Capacity adds a wet-bulb-driven term to account for moisture removal, and Latent Capacity is simply the difference between Total and Sensible. Sensible Heat Ratio (SHR) — the fraction of total capacity that is sensible rather than latent — is a ratio of two quantities that are both directly proportional to Airflow, so Airflow cancels out of the SHR formula entirely: doubling the CFM doubles both Sensible and Total Capacity by the same factor, leaving their ratio unchanged.
SHR is driven entirely by the four temperature inputs (Entering/Leaving Dry Bulb and Entering/Leaving Wet Bulb), not by how much air is moving. A higher SHR means the coil is doing more sensible cooling relative to dehumidification — useful for judging whether a coil selection will control humidity adequately in a given space. This is a simplified enthalpy approximation, not a full psychrometric calculation, and does not account for altitude, barometric pressure, or coil surface/fin geometry.
Inputs
AHRI 210/240: standard 80°F EDB; AHRI 550/590 chilled water coils: 95°F EDB / 75°F EWB
AHRI 210/240: standard LDB 55°F; commercial AHU 52–55°F; low-load/high-SHR applications 58–62°F
Results
Sensible Capacity
54,000 BTU/hr
Total Capacity
107,040 BTU/hr
How to Use This Calculator
- Enter Airflow, Entering Dry Bulb, and Leaving Dry Bulb.
- Set Entering Wet Bulb and Leaving Wet Bulb.
- Review Sensible Capacity (BTU/hr) and Total Capacity (BTU/hr).
- Use Latent Capacity (BTU/hr) to inform your decision, and Sensible Heat Ratio (SHR) — which depends only on the four temperatures, not on Airflow — to judge dehumidification performance.
How the result changes with Entering Dry Bulb
| Entering Dry Bulb | Sensible Capacity | Total Capacity |
|---|---|---|
| 40 | 0 BTU/hr | 53,040 BTU/hr |
| 60 | 10,800 BTU/hr | 63,840 BTU/hr |
| 120 | 140,400 BTU/hr | 193,440 BTU/hr |
What each input means
- Airflow
- Volume of air flowing across the coil in cubic feet per minute.
- Entering Dry Bulb
- Dry bulb temperature of air entering the cooling coil. ASHRAE design conditions: AHRI 210/240 standard rating at 80°F EDB / 67°F EWB for residential; AHRI 550/590 at 95°F EDB for chilled water coils.
- Leaving Dry Bulb
- Dry bulb temperature of air leaving the cooling coil. Standard AHRI conditions: 55°F LDB (leaving dry bulb) for residential split systems; 52–55°F for commercial AHUs. Cold aisle data centers target 65–68°F.
- Entering Wet Bulb
- Wet bulb temperature of air entering the coil.
- Leaving Wet Bulb
- Wet bulb temperature of air leaving the coil.
How this is calculated
Worked example, using the default values
- Identify Input Parameters4 parametersAirflow = 2000, Entering Dry Bulb = 80, Leaving Dry Bulb = 55, Entering Wet Bulb = 67 = 5 input(s) provided
- Calculate Sensible CapacitySensible Capacity54000 = 54000
- Calculate Total CapacityTotal Capacity107040 = 107040
- Calculate Latent CapacityLatent Capacity53040 = 53040
- Calculate Sensible Heat RatioSensible Heat Ratio0.504 = 0.504
Engine last updated . Checked against 3 independently-derived tests — how we verify calculators. Built by Paul Gunder, a software engineer, not a licensed financial, medical, or legal professional.
Frequently Asked Questions
Why doesn't increasing airflow change the Sensible Heat Ratio?
Sensible Heat Ratio is Sensible Capacity divided by Total Capacity, and both of those are calculated as CFM multiplied by a temperature-based factor. Since Airflow (CFM) appears as the same multiplier in both the numerator and denominator, it cancels out algebraically — SHR depends only on the entering and leaving dry-bulb and wet-bulb temperatures, not on how much air the coil is moving.
What does a low Sensible Heat Ratio mean for coil selection?
A lower SHR means a larger share of the coil's capacity is going toward removing moisture (latent cooling) rather than lowering temperature (sensible cooling). This matters in humid climates or high-occupancy spaces where dehumidification is a priority — a coil sized only from a sensible-load calculation could leave a space cool but clammy if the actual SHR need is lower than what the coil delivers.
How is Total Capacity different from just adding sensible and latent together?
Total Capacity is calculated directly from the dry-bulb and wet-bulb temperature drops using the coil's air-side enthalpy change, and Latent Capacity is then derived by subtracting Sensible Capacity from that total (floored at zero so it can't go negative). In other words, Total and Sensible are the two independently calculated figures, and Latent is the remainder — not the other way around.
Why do I need both dry bulb and wet bulb temperatures?
Dry bulb temperature alone only captures sensible heat — the part of cooling that lowers air temperature. Wet bulb temperature reflects moisture content as well, which is needed to estimate the coil's total (sensible plus latent) capacity per standard AHRI 210/240 and AHRI 550/590 rating-condition methodology. Without wet bulb readings, the calculator can't separate how much of the coil's work is dehumidification versus temperature drop.
Related Calculators
The questions that sit next to this one — chosen by subject, including calculators filed under a different category.
Chiller Sizing Calculator
Size chiller systems based on water flow rate, temperature differential, diversity factor, and efficiency metrics.
HVACPsychrometric Calculator
Calculate wet bulb temperature, dew point, humidity ratio, enthalpy, and specific volume from dry bulb and relative humidity.
Chemical EngineeringEnergy Balance Calculator
Calculate sensible heat, latent heat, total heat duty, and power requirements for process heating and cooling operations.
Process EngineeringEnergy Balance Calculator
Calculate steady-state energy balance for a process stream. Includes sensible heat (Q = mCpΔT), latent heat of phase change, and reaction heat contributions.
HVACBTU Calculator
Calculate heating and cooling BTU requirements for your room or home. Determine the right AC tonnage and furnace size based on room dimensions, insulation, and climate.
More in Construction & Building Trades.