Passive House Calculator
Evaluate whether your building meets Passivhaus (PHI) certification criteria for heating demand, cooling demand, primary energy, and airtightness.
About this calculator
Airtightness (ACH50) drives Heating Demand (kWh/m²/yr) through a fixed conversion, not a direct pass-through: this calculator divides ACH50 by 20 (the standard LBL rule-of- thumb factor relating a pressurized blower-door test to natural infiltration) before it ever enters the heat-loss formula, so a building's raw ACH50 number is always 20x larger than the natural air-change rate actually driving its infiltration heat loss. Average U-Value and Thermal Envelope Area combine multiplicatively into Heating Demand (kWh/m²/yr) -- doubling either one roughly doubles the transmission-loss term on its own -- but Floor Area plays a different role entirely: it sets the fixed internal-gains credit (about 20 kWh/m² per year, a standard residential occupancy/appliance heat assumption) that gets SUBTRACTED from total heat loss before dividing by that same floor area, so Floor Area affects Heating Demand (kWh/m²/yr) on both sides of the calculation at once. Passive Solar Gain (%) works as a straight percentage-offset against total heat loss (a building with 0% credited solar gain keeps its full heating demand; at 100%, this calculator floors net demand at zero rather than letting it go negative).
All four Passivhaus criteria -- Heating Demand, Cooling Demand, Primary Energy, and Airtightness -- are checked independently and ALL must pass for Passivhaus Certifiable to read 1; meeting three of the four still reports 0, with no partial credit shown in that single pass/fail figure. Those four thresholds (≤15 kWh/m²/yr specific heating/cooling demand, ≤60 kWh/m²/yr renewable primary energy demand, and ≤0.6 ACH50 airtightness) are the Passive House Institute's own published Passivhaus Classic Building Criteria, not a simplification invented for this calculator.
Inputs
Results
Heating Demand (kWh/m²/yr)
2.6
Figures current as of 2026. Source: Passive House Institute, Passive House Building Criteria (Version 10c) — specific space heating/cooling demand ≤ 15 kWh/(m²a), renewable primary energy demand (PER) ≤ 60 kWh/(m²a), airtightness n50 ≤ 0.6 h⁻¹ at 50 Pa
How to Use This Calculator
- Enter Floor Area and Thermal Envelope Area in sq ft.
- Enter Average U-Value of the entire envelope in Btu/hr·ft²·°F and Airtightness in ACH50.
- Enter Heating and Cooling Degree Days for your climate and Passive Solar Gain percentage.
- Review Specific Heating Demand in kWh/m²/yr — Passivhaus limit is ≤ 15 kWh/m²/yr.
- Check Peak Heating Load in W/m² and Passivhaus Certifiable status against all criteria.
How the result changes with Heating Degree Days (HDD65)
| Heating Degree Days (HDD65) | Heating Demand (kWh/m²/yr) |
|---|---|
| 3,000 | 0 |
| 4,500 | 0 |
| 9,000 | 13.8 |
| 15,000 | 36.4 |
What each input means
- Floor Area (sq ft)
- Treated floor area (TFA) of the building in square feet.
- Thermal Envelope Area (sq ft)
- Total area of the thermal envelope (walls + roof + floor + windows).
- Average U-Value (Btu/hr·ft²·°F)
- Area-weighted average U-value of the entire thermal envelope. R-35 ≈ 0.028, R-50 ≈ 0.020.
- Airtightness (ACH50)
- Air changes per hour at 50 Pascals pressure. Passivhaus requires ≤ 0.6.
- Heating Degree Days (HDD65)
- Annual heating degree days (base 65°F) for your climate. Denver ~6000, Minneapolis ~8000.
- Cooling Degree Days (CDD65)
- Annual cooling degree days (base 65°F). Phoenix ~4000, Seattle ~200.
- Passive Solar Gain (%)
- Percentage of heating load offset by passive solar gains through south-facing glazing.
What each result means
- Heating Demand (kWh/m²/yr)
- Specific annual heating demand. Passivhaus limit: ≤ 15 kWh/m²/yr.
- Cooling Demand (kWh/m²/yr)
- Specific annual cooling demand. Passivhaus limit: ≤ 15 kWh/m²/yr.
- Primary Energy (kWh/m²/yr)
- Total specific primary energy including DHW, lighting, appliances. Passivhaus limit: ≤ 60 kWh/m²/yr.
- Airtightness (ACH50)
- Blower door test result. Passivhaus limit: ≤ 0.6 ACH50.
- Peak Heating Load (W/m²)
- Peak heating power demand. Passivhaus limit: 10 W/m².
- Passivhaus Certifiable
- 1 = meets all criteria, 0 = does not meet one or more criteria.
How this is calculated
Worked example, using the default values
- Identify Input Parameters4 parametersFloor Area (sq ft) = 1800, Thermal Envelope Area (sq ft) = 4000, Average U-Value (Btu/hr·ft²·°F) = 0.028, Airtightness (ACH50) = 0.5 = 7 input(s) provided
- Calculate Heating Demand2.6 = 2.6
- Calculate Cooling Demand2.4 = 2.4
- Calculate Primary EnergyPrimary Energy = totalPrimaryEnergy / floorAreaM234.9 = 34.9
Figures and sources
- Passive House Institute (PHI) Passivhaus Classic certification criteria (2026) — Passive House Institute, Passive House Building Criteria (Version 10c) — specific space heating/cooling demand ≤ 15 kWh/(m²a), renewable primary energy demand (PER) ≤ 60 kWh/(m²a), airtightness n50 ≤ 0.6 h⁻¹ at 50 Pa
Engine last updated . Checked against 3 independently-derived tests — how we verify calculators. Built by Paul Gunder, a software engineer, not a licensed financial, medical, or legal professional.
Frequently Asked Questions
Why does the ACH50 airtightness number feel so much bigger than the infiltration effect it seems to have?
Because ACH50 is a pressurized test result, not the building's natural air-change rate. This calculator divides your Airtightness (ACH50) input by 20 -- the standard LBL (Lawrence Berkeley Lab) conversion factor -- before using it in the infiltration heat-loss formula, since air moves through leaks far faster under the blower door's 50 Pascal test pressure than it does under everyday wind and stack-effect pressures. A building at the Passivhaus 0.6 ACH50 limit has a natural infiltration rate of just 0.03 air changes per hour, which is why its contribution to total heat loss is smaller than the raw 0.6 figure might suggest.
Does Floor Area (sq ft) always lower Heating Demand (kWh/m²/yr) when I increase it?
Not necessarily -- Floor Area affects the calculation on both sides at once. It sets the internal-gains credit (about 20 kWh per square meter per year) that gets subtracted from total heat loss, AND it's the denominator Heating Demand (kWh/m²/yr) is divided by. A larger floor area gets a proportionally larger internal-gains credit, but it's also spreading (and dividing) the same transmission and infiltration losses across more area -- which direction wins depends on how Thermal Envelope Area and Average U-Value compare to the floor area you entered.
Why does 100% Passive Solar Gain not bring Heating Demand (kWh/m²/yr) all the way to a large negative number?
Because this calculator floors Net Heating Demand at zero rather than letting solar and internal gains overshoot total heat loss into negative territory. Passive Solar Gain (%) is applied as a straight percentage offset against total heat loss (before internal gains), so raising it keeps lowering Heating Demand (kWh/m²/yr) right up until the combined gains equal or exceed the loss -- at that point the calculator reports 0, not a negative heating demand, which wouldn't represent anything physically meaningful.
If a building meets three of the four Passivhaus criteria, does Passivhaus Certifiable show partial credit?
No -- it's strictly all-or-nothing. Heating Demand, Cooling Demand, Primary Energy, and Airtightness are each checked against their own Passivhaus limit (≤15, ≤15, ≤60 kWh/m²/yr, and ≤0.6 ACH50 respectively) independently, and Passivhaus Certifiable only reads 1 when every one of the four passes. Missing just one criterion -- even by a small margin -- reports the same 0 as missing all four; the individual output fields are where you'd look to see which specific criterion is the problem. These four limits come directly from the Passive House Institute's published Building Criteria for Passivhaus Classic certification, not from this calculator.
Related Calculators
The questions that sit next to this one — chosen by subject, including calculators filed under a different category.
Passive Solar Design Calculator
Thermal mass and window sizing for passive solar earthen buildings.
Green BuildingLEED Points Calculator
Estimate your LEED v4.1 certification level from credit category point projections across all seven scoring categories.
Income OptimizationPassive Income Goal Calculator
Calculate how much you need invested to generate your target monthly passive income. See your progress toward financial independence and how long it will take to reach your goal.
Green BuildingNet Zero Building Calculator
Analyze whether your building can achieve net-zero energy status by comparing annual consumption against on-site renewable generation.
Green BuildingEmbodied Carbon Calculator
Calculate A1-A3 embodied carbon (kgCO2e) for your building's structural and envelope materials — concrete, steel, timber, masonry, glass, and insulation.
More in Construction & Building Trades.