Voltage Drop Calculator (Residential)

Calculate voltage drop for residential wiring and check compliance with the NEC 3% recommendation.

Inputs

ft
A

Results

Voltage Drop

3.57 V

Drop Percentage2.98%
Voltage at Load116.43 V
NEC 3% Compliant1
Power Loss53.6 W
How to Use This Calculator
  1. Select Wire Gauge (AWG) from the dropdown — lower AWG = thicker wire.
  2. Enter One-Way Distance (ft) from panel to load.
  3. Input Current (amps) drawn by the load.
  4. Review Actual Voltage Drop (%) — NEC recommends keeping this below 3% for branch circuits.
  5. If voltage drop exceeds 3%, select the next heavier AWG and recalculate.

How the result changes with One-Way Distance

One-Way DistanceVoltage Drop
1014.81 V
35116.72 V
65030.97 V
90042.88 V

What each input means

Wire Gauge (AWG)
AWG wire gauge of the installed or planned conductor.
One-Way Distance
One-way distance from panel to the load in feet.
Current
Current draw of the circuit load in amps.
System Voltage
Nominal system voltage of the circuit.

How this is calculated

Worked example, using the default values

  1. Identify Input Parameters
    4 parameters
    Wire Gauge (AWG) = 12, One-Way Distance = 75, Current = 15, System Voltage = 120 = 4 input(s) provided
  2. Calculate Voltage Drop
    Voltage Drop
    3.57 = 3.57
  3. Calculate Drop Percentage
    Drop Percentage
    2.98 = 2.98
  4. Calculate Voltage at Load
    Voltage at Load
    116.43 = 116.43