Feeder Sizing Calculator
Feeder conductor size from load amps and distance, with voltage drop check per NEC 215.2.
About this calculator
This calculator sizes a feeder two different ways and keeps the more conservative result. First it looks up the smallest conductor whose ampacity meets Load current (amps) directly against Table 310.16 of NFPA 70, the National Electrical Code (NEC). Second, it computes Min cmil for VD limit from the voltage-drop formula Vd = phaseFactor x K x I x L / cmil (K = 12.9 ohm-cmil/ft for copper, 21.2 for aluminum; phaseFactor is 2 for single-phase or the square root of 3 for three-phase) and picks the smallest conductor whose circular-mil area meets that requirement. Whichever of the two picks is the larger conductor becomes the final selection, and Sizing Basis reports which check actually drove it. Min cmil for VD limit itself is a clean product of three inputs: Load current (amps) and One-way distance (ft) both raise it in direct proportion (doubling either one doubles the required cmil area), while Max voltage drop (%) lowers it, since a looser allowed drop needs less copper or aluminum to stay within it. Which of the two sizing checks (ampacity or voltage drop) actually governs the final conductor size depends on the combination of load, distance, and the allowed drop percentage -- at this calculator's default inputs (200 A, 150 ft, 480 V three-phase, 3% max drop), the ampacity check governs for both conductor materials, and One-way distance, System voltage, and Max voltage drop have no effect on the selected conductor size while ampacity governs (they still move the displayed Min cmil for VD limit and Actual voltage drop figures, just not the selection itself).
Conductor material is different: it still moves the final selection directly at the defaults, because copper and aluminum have their own separate ampacity table rows -- a 200 A copper load lands on 3/0 AWG (200 A ampacity) while the same 200 A aluminum load lands two full table rows higher on 250 kcmil (205 A ampacity), even though the ampacity check governs for both. At longer distances or a tighter drop limit the voltage-drop check takes over and distance, voltage, and drop percentage start to matter directly as well. If the required ampacity or cmil area exceeds the largest listed conductor (750 kcmil), Exceeds conductor table flags it and Sizing Basis reports "(exceeds table)" so the displayed single-conductor selection is never mistaken for an adequate one. Parallel conductor runs is derived from ampacity alone (load current divided by the largest conductor's ampacity, rounded up), so it only tells you how many sets to run in parallel when Sizing Basis reads "Ampacity (exceeds table)" -- the calculator does not account for conduit fill limits, ambient temperature derating, or bundling adjustments that a full NEC 310.15 analysis would require. When Sizing Basis instead reads "Voltage drop (exceeds table)," Parallel conductor runs can still read 1 even though a single run isn't adequate, because voltage drop and ampacity are independent checks; the fix there is a shorter run, a higher system voltage, a higher allowed Max voltage drop, or splitting the load, not more parallel conductors. Actual voltage drop (V) and (%) account for Parallel conductor runs by dividing the single-conductor drop by the number of parallel runs, since each run only carries a fraction of the total current.
Inputs
Results
Conductor ampacity (A)
200
Figures current as of 2026. Source: National Fire Protection Association, NFPA 70, National Electrical Code (NEC), 2026 Edition
How to Use This Calculator
- Enter the total feeder load in amperes from your panel schedule or load calculation.
- Enter the one-way distance in feet from the source panel to the load panel or equipment.
- Set the system voltage (208, 240, 277, or 480 V) and phase count (1 or 3).
- Select conductor material — copper (1) or aluminum (2) — and the maximum allowable voltage drop percentage (NEC recommends 3%).
- Read the selected conductor ampacity, actual voltage drop in volts and percent, and whether parallel runs are required.
How the result changes with Load current (amps)
| Load current (amps) | Conductor ampacity (A) |
|---|---|
| 100 | 100 |
| 150 | 150 |
| 300 | 310 |
| 500 | 475 |
What each input means
- Load current (amps)
- Total feeder load in amperes.
- One-way distance (ft)
- One-way distance from source to load in feet.
- System voltage (V)
- System voltage (208, 240, 277, 480 typical).
- Phases (1 or 3)
- Single-phase (1) or three-phase (3).
- Material (1=Cu, 2=Al)
- 1 = Copper (K=12.9), 2 = Aluminum (K=21.2).
- Max voltage drop (%)
- NEC recommends 3% max for feeders (5% total branch+feeder).
What each result means
- Conductor ampacity (A)
- Ampacity of the selected conductor from NEC Table 310.16.
- Actual voltage drop (V)
- Calculated voltage drop using Vd = 2KIL/cmil (or sqrt(3) for 3-phase).
- Actual voltage drop (%)
- Voltage drop as percentage of system voltage.
- Min cmil for VD limit
- Minimum conductor cmil area to stay within voltage drop limit.
- Parallel conductor runs
- Number of parallel conductor sets if single set insufficient.
- Load current (A)
- Input load current for reference.
- Exceeds conductor table (1=Yes)
- 1 if the required ampacity or voltage-drop cmil area exceeds the largest listed conductor (750 kcmil) -- the displayed conductor and Sizing Basis are only the largest table entry shown for reference, NOT a safe single-run recommendation. If Sizing Basis reads "Ampacity (exceeds table)," check Parallel conductor runs for how many sets you need. If it reads "Voltage drop (exceeds table)," Parallel conductor runs is derived from ampacity alone and can still read 1 -- more parallel runs won't fix a voltage-drop problem; instead shorten the run, raise the system voltage, allow a higher Max voltage drop, or split the load. Consult an electrical engineer for a custom or busway design.
How this is calculated
Worked example, using the default values
- Identify Input Parameters4 parametersLoad current (amps) = 200, One-way distance (ft) = 150, System voltage (V) = 480, Phases (1 or 3) = 3 = 6 input(s) provided
- Calculate Conductor ampacity200 = 200
- Calculate Actual voltage dropActual voltage drop = (phaseFactor * K * loadAmps * distanceFt) / (finalConductor.cmil * parallelRuns)3.99 = 3.99
- Calculate Actual voltage dropActual voltage drop = (actualVd / voltage) * 1000.83 = 0.83
Figures and sources
- Conductor ampacity (Table 310.16) and feeder/voltage-drop rules (Articles 210, 215) (2026) — National Fire Protection Association, NFPA 70, National Electrical Code (NEC), 2026 Edition
Engine last updated . Checked against 1 independently-derived test — how we verify calculators. Built by Paul Gunder, a software engineer, not a licensed financial, medical, or legal professional.
Frequently Asked Questions
Why does load current move the minimum conductor size in two different ways?
Load current (amps) feeds both sizing checks independently: it directly compares against the NEC Table 310.16 ampacity ratings, and it also multiplies into Min cmil for VD limit, the voltage-drop-based sizing requirement. The calculator runs both checks and keeps whichever recommends the larger conductor, so a higher load current can push the result up through either path.
Does increasing the maximum allowed voltage drop let me use a smaller conductor?
Yes, within limits -- Max voltage drop (%) sits in the denominator of the voltage- drop sizing formula, so raising it lowers Min cmil for VD limit and can allow a smaller conductor by that check. But the ampacity-based check (driven by Load current alone) is unaffected by the voltage-drop percentage, and the calculator always keeps the larger of the two recommendations, so a very loose voltage-drop allowance can't shrink the conductor below what ampacity alone requires.
What does Sizing Basis tell me?
It reports which of the two checks actually determined the selected conductor: "Ampacity" means the ampacity rating in NEC (NFPA 70) Table 310.16 governed, while "Voltage drop" means the calculated Min cmil for VD limit needed a larger conductor than ampacity alone would require. Longer One-way distance and tighter Max voltage drop limits both push the result toward "Voltage drop." If the load is large enough that either check would need a conductor bigger than the largest listed entry (750 kcmil), Sizing Basis instead reports "Ampacity (exceeds table)" or "Voltage drop (exceeds table)," and Exceeds conductor table reads 1. If it reads "Ampacity (exceeds table)," check Parallel conductor runs for how many conductor sets you actually need -- that figure comes from load current divided by the largest conductor's ampacity. If it reads "Voltage drop (exceeds table)," Parallel conductor runs is still computed from ampacity alone and can read 1 even though a single run isn't adequate; splitting into more parallel runs won't fix a voltage-drop problem -- use a shorter run, a higher system voltage, a higher allowed Max voltage drop, or split the load instead.
What happens if the load exceeds the largest listed conductor's ampacity?
Parallel conductor runs shows how many conductor sets you need to run in parallel -- calculated as the load current divided by the largest available conductor's ampacity, rounded up. Above 750 kcmil (the largest NEC Table 310.16 entry in this tool), a single run is no longer physically adequate for very large loads, and splitting the current across multiple parallel conductor sets is standard practice rather than an edge case. Exceeds conductor table also reads 1 in this situation, as an explicit flag matching the pattern used elsewhere in this calculator suite.
Related Calculators
The questions that sit next to this one — chosen by subject, including calculators filed under a different category.
Electrical Panel Schedule Calculator
Panel load calculation with NEC demand factors for lighting, receptacles, motors, and HVAC.
Construction ElectricalData Cable Calculator
Cable runs, conduit fill per NEC Table 1, and pathway sizing from network drop count.
Science & EngineeringVoltage Drop Calculator
Calculate voltage drop in electrical wiring based on wire gauge, length, current, and material. Ensure your circuits meet NEC recommendations.
Hobby ElectronicsWire Gauge Calculator
Wire AWG from current capacity and voltage drop.
Electrical & PlumbingVoltage Drop Calculator (Residential)
Calculate voltage drop for residential wiring and check compliance with the NEC 3% recommendation.
More in Construction & Building Trades.