Arc Flash Calculator
Estimate arc flash incident energy, flash boundary, PPE category, and required cal rating per IEEE 1584.
Inputs
NFPA 70E / IEEE 1584: switchgear 91 cm; MCC/panels 46 cm; open bus/switch 91–183 cm
IEEE 1584: current-limiting fuse 0.008–0.017 s; electronic trip CB 0.05–0.1 s; thermal-mag CB 0.1–0.5 s
Results
Incident Energy
15.84 cal/cm²
PPE Category
3
How to Use This Calculator
- Enter the Bolted Fault Current in amperes — obtain this from a short-circuit study or the utility's available fault current at the service entrance.
- Enter the Working Distance in cm from the potential arc source to the worker's face: switchgear ≈ 91 cm, MCC/panel ≈ 46 cm.
- Enter the Arc Duration in seconds — this is the clearing time of the upstream protective device (breaker trip time or fuse melt time).
- Enter the System Voltage in volts and the Gap Between Conductors in mm: LV switchgear ≈ 32 mm, MCC ≈ 25 mm.
- Read the Incident Energy in cal/cm² and the PPE Category (0–4) per NFPA 70E to select appropriate arc-rated PPE.
- Note the Arc Flash Boundary in mm — workers within this distance must wear full arc-rated PPE; beyond it, only basic protection is required.
How the result changes with Working Distance
| Working Distance | Incident Energy | PPE Category |
|---|---|---|
| 29 | 33.77 cal/cm² | 4 |
| 77 | 6.8 cal/cm² | 2 |
| 134 | 2.74 cal/cm² | 1 |
| 181 | 1.67 cal/cm² | 1 |
What each input means
- Bolted Fault Current
- Available three-phase bolted fault current at the equipment.
- Working Distance
- Distance from potential arc source to worker per NFPA 70E Table 130.7(C)(15)(a) and IEEE 1584. Typical: open switchgear 91 cm (36"); MCCs/panels 46 cm (18"); motor control centers 46 cm; NEMA type panelboards 46 cm.
- Arc Duration
- Clearing time of the upstream protective device per NFPA 70E and IEEE 1584. Shorter clearing time reduces incident energy. Typical: electronic trip breaker 0.05–0.1 s; thermal-magnetic 0.1–0.5 s; current-limiting fuse 0.008–0.017 s.
- System Voltage
- Nominal system voltage at the equipment.
- Gap Between Conductors
- Gap between bus conductors. LV switchgear: 32 mm, MCC: 25 mm, panel: 25 mm.
How this is calculated
Worked example, using the default values
- Identify Input Parameters4 parametersBolted Fault Current = 25000, Working Distance = 46, Arc Duration = 0.1, System Voltage = 480 = 5 input(s) provided
- Calculate Incident EnergyIncident Energy = Math15.84 = 15.84
- Calculate PPE Category3 = 3
- Calculate Arc Flash BoundaryArc Flash Boundary = Math2216 = 2216
- Calculate Required Cal RatingRequired Cal Rating25 = 25
Related Calculators
The questions that sit next to this one — chosen by subject, including calculators filed under a different category.
Short Circuit Current Calculator
Calculate available fault current, X/R ratio, and interrupting duty at a point downstream of a transformer.
Electrical EngineeringGrounding System Calculator
Design grounding electrode systems: calculate single rod resistance, parallel rod resistance, touch and step voltages.
Electrical EngineeringTransformer Sizing Calculator
Size single-phase and three-phase transformers: calculate required KVA, full load current, and select next standard size.
More in Engineering.