Skip to main content
Calcimator

Arc Flash Calculator

Estimate arc flash incident energy, flash boundary, PPE category, and required cal rating per IEEE 1584.

Inputs

A
in

NFPA 70E / IEEE 1584: switchgear 91 cm; MCC/panels 46 cm; open bus/switch 91–183 cm

seconds

IEEE 1584: current-limiting fuse 0.008–0.017 s; electronic trip CB 0.05–0.1 s; thermal-mag CB 0.1–0.5 s

V
mm

Results

Incident Energy

15.84 cal/cm²

PPE Category

3

Arc Flash Boundary2,216 mm
Required Cal Rating25 cal/cm²
How to Use This Calculator
  1. Enter the Bolted Fault Current in amperes — obtain this from a short-circuit study or the utility's available fault current at the service entrance.
  2. Enter the Working Distance in cm from the potential arc source to the worker's face: switchgear ≈ 91 cm, MCC/panel ≈ 46 cm.
  3. Enter the Arc Duration in seconds — this is the clearing time of the upstream protective device (breaker trip time or fuse melt time).
  4. Enter the System Voltage in volts and the Gap Between Conductors in mm: LV switchgear ≈ 32 mm, MCC ≈ 25 mm.
  5. Read the Incident Energy in cal/cm² and the PPE Category (0–4) per NFPA 70E to select appropriate arc-rated PPE.
  6. Note the Arc Flash Boundary in mm — workers within this distance must wear full arc-rated PPE; beyond it, only basic protection is required.

How the result changes with Working Distance

Working DistanceIncident EnergyPPE Category
2933.77 cal/cm²4
776.8 cal/cm²2
1342.74 cal/cm²1
1811.67 cal/cm²1

What each input means

Bolted Fault Current
Available three-phase bolted fault current at the equipment.
Working Distance
Distance from potential arc source to worker per NFPA 70E Table 130.7(C)(15)(a) and IEEE 1584. Typical: open switchgear 91 cm (36"); MCCs/panels 46 cm (18"); motor control centers 46 cm; NEMA type panelboards 46 cm.
Arc Duration
Clearing time of the upstream protective device per NFPA 70E and IEEE 1584. Shorter clearing time reduces incident energy. Typical: electronic trip breaker 0.05–0.1 s; thermal-magnetic 0.1–0.5 s; current-limiting fuse 0.008–0.017 s.
System Voltage
Nominal system voltage at the equipment.
Gap Between Conductors
Gap between bus conductors. LV switchgear: 32 mm, MCC: 25 mm, panel: 25 mm.

How this is calculated

Worked example, using the default values

  1. Identify Input Parameters
    4 parameters
    Bolted Fault Current = 25000, Working Distance = 46, Arc Duration = 0.1, System Voltage = 480 = 5 input(s) provided
  2. Calculate Incident Energy
    Incident Energy = Math
    15.84 = 15.84
  3. Calculate PPE Category
    3 = 3
  4. Calculate Arc Flash Boundary
    Arc Flash Boundary = Math
    2216 = 2216
  5. Calculate Required Cal Rating
    Required Cal Rating
    25 = 25

The questions that sit next to this one — chosen by subject, including calculators filed under a different category.

More in Engineering.