Short Circuit Current Calculator
Calculate available fault current, X/R ratio, and interrupting duty at a point downstream of a transformer.
Inputs
kVA
%Z
ANSI C57.12.00: 75–333 kVA: 4.0–5.5%Z; 500–1,000 kVA: 5.5–6.0%Z; 1,000–5,000 kVA: 5.75–7.5%Z
V
ft
mm²
phase
Results
Available Fault Current
14,648 A
Min. Withstand Rating
15,000 A
X/R Ratio0.91
Interrupting Duty14,648 A
How to Use This Calculator
- Enter the Transformer KVA rating and its Percent Impedance (%Z) from the transformer nameplate — typical 5–6% for 1,000+ kVA units.
- Enter the Secondary System Voltage in volts (e.g., 208 or 480 V).
- Enter the Cable Length in meters from the transformer to the fault point and the Cable Size in mm².
- Select the Number of Phases (1 or 3).
- Read the Available Fault Current in amperes — use this to verify breaker and switchgear interrupting ratings.
- Use the Minimum Withstand Rating in amperes to confirm buses, lugs, and equipment can survive a bolted fault without damage.
How the result changes with Transformer Impedance
| Transformer Impedance | Available Fault Current | Min. Withstand Rating |
|---|---|---|
| 2.4 | 24,743 A | 25,000 A |
| 5.9 | 14,386 A | 15,000 A |
| 10 | 9,652 A | 10,000 A |
| 14 | 7,307 A | 8,000 A |
What each input means
- Transformer KVA
- Rated KVA of the upstream transformer.
- Transformer Impedance
- Transformer percent impedance from nameplate per ANSI/IEEE C57.12.00. Typical values: 15–75 kVA: 2.0–3.5%; 75–333 kVA: 4.0–5.5%; 500–1,000 kVA: 5.5–6.0%; 1,000–5,000 kVA: 5.75–7.5%. Higher %Z = lower fault current.
- System Voltage
- Secondary system voltage (e.g., 208, 480V).
- Cable Length to Fault
- Distance from transformer to the point of fault calculation.
- Cable Size
- Cross-sectional area of the cable conductor in mm².
- Number of Phases
- Select 1 for single-phase or 3 for three-phase.
How this is calculated
Worked example, using the default values
- Identify Input Parameters4 parametersTransformer KVA = 1000, Transformer Impedance = 5.75, System Voltage = 480, Cable Length to Fault = 30 = 6 input(s) provided
- Calculate Available Fault CurrentAvailable Fault Current14648 = 14648
- Calculate Min. Withstand RatingMin. Withstand Rating15000 = 15000
- Calculate X/R RatioX/R Ratio0.91 = 0.91
- Calculate Interrupting DutyInterrupting Duty14648 = 14648
Related Calculators
The questions that sit next to this one — chosen by subject, including calculators filed under a different category.
Electrical Engineering
Arc Flash Calculator
Estimate arc flash incident energy, flash boundary, PPE category, and required cal rating per IEEE 1584.
Electrical EngineeringTransformer Sizing Calculator
Size single-phase and three-phase transformers: calculate required KVA, full load current, and select next standard size.
Electrical EngineeringMotor Starting Current Calculator
Calculate motor full load amps, starting inrush current, voltage drop during starting, and starting KVA demand.
More in Engineering.