Emergency Generator Calculator
Size emergency generators with altitude and temperature derating, fuel consumption, and runtime estimates.
Inputs
NFPA 110 / IEEE Std 446: standard generator 0.8 PF rating; kW = kVA × 0.8; size in kW not kVA
ISO 8528-1: no derating ≤1,000 m; ~3–4% per 300 m above 1,000 m; at 2,000 m ~10–14% derating
Results
Required Generator Size
300 kW
≈ 20 homes' peak draw
Required KVA
375 kVA
How to Use This Calculator
- Enter the Total Critical Load in kW — sum all loads that must remain on during a power outage.
- Enter the Largest Motor Starting Load in kW — motor inrush is typically 3× running kW and determines the generator's transient kVA requirement.
- Set the Power Factor — standard standby generators are rated at 0.8 PF.
- Enter the Site Altitude in meters above sea level — derating begins above 1,000 m at approximately 3.5% per 300 m.
- Enter the Maximum Ambient Temperature in °C — derating begins above 40°C.
- Read the Required Generator Size in kW and kVA, then check Fuel Consumption (L/hr) and estimated Runtime from a 500L tank to plan fuel logistics.
How the result changes with Total Critical Load
| Total Critical Load | Required Generator Size | Required KVA |
|---|---|---|
| 1,001 | 1,261.2 kW | 1,576.5 kVA |
| 3,501 | 4,261.2 kW | 5,326.5 kVA |
| 6,500 | 7,860 kW | 9,825 kVA |
| 9,000 | 10,860 kW | 13,575 kVA |
What each input means
- Total Critical Load
- Sum of all critical loads that must be powered during an outage.
- Largest Motor Starting Load
- Additional KW demand from the largest motor starting (typically 3× running KW).
- Power Factor
- Generator rated power factor per NFPA 110 and IEEE Std 446 (Orange Book). Standard emergency generators are rated at 0.8 PF per NFPA 110. kW = kVA × PF; a 0.8 PF generator produces more kVA than kW nameplate.
- Site Altitude
- Elevation above sea level. Generator capacity decreases with altitude due to reduced air density per ISO 8528-1. Derating: ~3–4% per 300 m (1,000 ft) above 1,000 m (3,281 ft); consult manufacturer for exact correction factors.
- Maximum Ambient Temperature
- Highest expected ambient temperature. Derating starts above 40°C.
How this is calculated
Worked example, using the default values
- Identify Input Parameters4 parametersTotal Critical Load = 200, Largest Motor Starting Load = 50, Power Factor = 0.8, Site Altitude = 200 = 5 input(s) provided
- Calculate Required Generator SizeRequired Generator Size300 = 300
- Calculate Required KVARequired KVA375 = 375
- Calculate Derated CapacityDerated Capacity300 = 300
- Calculate Fuel ConsumptionFuel Consumption60.75 = 60.75
Related Calculators
The questions that sit next to this one — chosen by subject, including calculators filed under a different category.
Transformer Sizing Calculator
Size single-phase and three-phase transformers: calculate required KVA, full load current, and select next standard size.
Electrical EngineeringDemand Load Calculator
Calculate residential service demand load per NEC Article 220: general lighting, appliances, HVAC, and service size.
Data CenterGenerator Sizing (DC) Calculator
Size standby generators for data center backup power with altitude/temperature derating and redundancy configurations.
Emergency ManagementEmergency Generator Fuel Calculator
Calculate fuel storage needs for emergency generator runtime based on generator size, load, fuel type, and duration.
Event ProductionEvent Power Calculator
Calculate total power requirements for events including lighting, sound, catering, generator sizing, and circuit counts.
More in Engineering.