Skip to main content
Calcimator

Emergency Generator Calculator

Size emergency generators with altitude and temperature derating, fuel consumption, and runtime estimates.

Inputs

kW
kW

NFPA 110 / IEEE Std 446: standard generator 0.8 PF rating; kW = kVA × 0.8; size in kW not kVA

ft

ISO 8528-1: no derating ≤1,000 m; ~3–4% per 300 m above 1,000 m; at 2,000 m ~10–14% derating

°F

Results

Required Generator Size

300 kW

≈ 20 homes' peak draw

Required KVA

375 kVA

Derated Capacity300 kW
Fuel Consumption (75% load)60.75 L/hr
Runtime (500L tank)8.2 hours
How to Use This Calculator
  1. Enter the Total Critical Load in kW — sum all loads that must remain on during a power outage.
  2. Enter the Largest Motor Starting Load in kW — motor inrush is typically 3× running kW and determines the generator's transient kVA requirement.
  3. Set the Power Factor — standard standby generators are rated at 0.8 PF.
  4. Enter the Site Altitude in meters above sea level — derating begins above 1,000 m at approximately 3.5% per 300 m.
  5. Enter the Maximum Ambient Temperature in °C — derating begins above 40°C.
  6. Read the Required Generator Size in kW and kVA, then check Fuel Consumption (L/hr) and estimated Runtime from a 500L tank to plan fuel logistics.

How the result changes with Total Critical Load

Total Critical LoadRequired Generator SizeRequired KVA
1,0011,261.2 kW1,576.5 kVA
3,5014,261.2 kW5,326.5 kVA
6,5007,860 kW9,825 kVA
9,00010,860 kW13,575 kVA

What each input means

Total Critical Load
Sum of all critical loads that must be powered during an outage.
Largest Motor Starting Load
Additional KW demand from the largest motor starting (typically 3× running KW).
Power Factor
Generator rated power factor per NFPA 110 and IEEE Std 446 (Orange Book). Standard emergency generators are rated at 0.8 PF per NFPA 110. kW = kVA × PF; a 0.8 PF generator produces more kVA than kW nameplate.
Site Altitude
Elevation above sea level. Generator capacity decreases with altitude due to reduced air density per ISO 8528-1. Derating: ~3–4% per 300 m (1,000 ft) above 1,000 m (3,281 ft); consult manufacturer for exact correction factors.
Maximum Ambient Temperature
Highest expected ambient temperature. Derating starts above 40°C.

How this is calculated

Worked example, using the default values

  1. Identify Input Parameters
    4 parameters
    Total Critical Load = 200, Largest Motor Starting Load = 50, Power Factor = 0.8, Site Altitude = 200 = 5 input(s) provided
  2. Calculate Required Generator Size
    Required Generator Size
    300 = 300
  3. Calculate Required KVA
    Required KVA
    375 = 375
  4. Calculate Derated Capacity
    Derated Capacity
    300 = 300
  5. Calculate Fuel Consumption
    Fuel Consumption
    60.75 = 60.75

The questions that sit next to this one — chosen by subject, including calculators filed under a different category.

More in Engineering.