Fire Department Connection Calculator
FDC requirements from system type and demand.
Inputs
Results
Total FDC flow (GPM)
500
FDC connections needed
1
Inlet connections2
Required FD inlet pressure (PSI)136.7
Elevation pressure (PSI)21.7
FD pumper capacity OKYes
Hydrant distance OKYes
Check valve requiredYes
Signage typeAUTO SPKR & STANDPIPE
4" Storz sufficientYes
Recommended Connection Desc2 × 2.5" Siamese or 1 × 4" Storz
Drain Valve RequiredYes
How to Use This Calculator
- Enter System type served, Sprinkler demand (GPM), and Standpipe demand (GPM).
- Set Building height (ft), Distance to hydrant (ft), and FDC style.
- Review Total FDC flow (GPM) and FDC connections needed.
- Use Inlet connections and Required FD inlet pressure (PSI) to inform your decision.
How the result changes with Standpipe demand (GPM)
| Standpipe demand (GPM) | Total FDC flow (GPM) | FDC connections needed |
|---|---|---|
| 500 | 500 | 1 |
| 1,750 | 1,750 | 1 |
| 3,250 | 3,250 | 1 |
| 4,500 | 4,500 | 1 |
What each input means
- System type served
- 1=Sprinkler only, 2=Standpipe only, 3=Combined, 4=Separate sprinkler + standpipe.
- Sprinkler demand (GPM)
- Total sprinkler system flow demand from hydraulic calculations.
- Standpipe demand (GPM)
- Standpipe system flow demand per NFPA 14.
- Building height (ft)
- Height from FDC to highest outlet served.
- Distance to hydrant (ft)
- Distance from FDC to nearest fire hydrant. Must be ≤100 ft per NFPA.
- FDC style
- 1=Wall-mounted, 2=Freestanding post, 3=Pit/flush type.
What each result means
- Total FDC flow (GPM)
- Total flow the FDC must accommodate.
- FDC connections needed
- Number of separate FDC assemblies required.
- Inlet connections
- Number of 2.5" or 4" inlets needed.
- Required FD inlet pressure (PSI)
- Pressure the fire department pumper must deliver at the FDC.
- Elevation pressure (PSI)
- Static head from FDC to highest outlet.
- FD pumper capacity OK
- 1=Typical pumper (150 PSI) can supply, 0=May need relay pumping.
- Hydrant distance OK
- 1=Within 100 ft, 0=Exceeds NFPA requirement.
- Check valve required
- Always 1. Check valve prevents backflow from system into FDC.
- Signage type
- 1=AUTO SPKR, 2=STANDPIPE, 3=AUTO SPKR & STANDPIPE.
- 4" Storz sufficient
- 1=Single 4" Storz coupling is adequate, 0=Need multiple connections.
How this is calculated
Worked example, using the default values
- Identify Input Parameters4 parametersSystem type served = 3, Sprinkler demand (GPM) = 250, Standpipe demand (GPM) = 500, Building height (ft) = 50 = 6 input(s) provided
- Calculate Total FDC flowTotal FDC flow500 = 500
- Calculate FDC connections neededFDC connections needed1 = 1
- Calculate Inlet connections2 = 2
- Calculate Required FD inlet pressureRequired FD inlet pressure = residualPSI + elevationPressurePSI + frictionEstimatePSI136.7 = 136.7
Related Calculators
The questions that sit next to this one — chosen by subject, including calculators filed under a different category.
Fire Protection
Standpipe System Design Calculator
Standpipe class and sizing from building height and use.
Fire ProtectionFire Water Storage Calculator
Fire water tank capacity from sprinkler demand and fire flow.
Fire SafetyFire Sprinkler Design Calculator
Calculate sprinkler head count, spacing, design density, and pipe sizing per NFPA 13.
Fire ProtectionFire Door Rating Calculator
Required fire rating from wall construction and occupancy.
Commercial PlumbingFire Sprinkler Pipe Sizing Calculator
Size fire sprinkler piping per NFPA 13 based on hazard classification, sprinkler count, and coverage area.
More in Safety, Compliance & Emergency.