Design hot/cold aisle containment layout from rack count, power density, and aisle dimensions.

Inputs

Results

Total racks

40

Total IT load (kW)280
Required airflow (CFM)35,385
Floor area (ft²)560
Cold aisle velocity (FPM)553
Return air temp (°F)89
Power density (W/ft²)500
Containment efficiency (%)85
How to Use This Calculator
  1. Enter the number of racks and average kW per rack.
  2. Set aisle width in feet and containment type (cold aisle vs. hot aisle).
  3. Input CRAC/CRAH unit CFM per ton rating.
  4. Review the CFM required per rack and number of cooling units needed.
  5. Verify cold aisle supply air temperature meets ASHRAE A1-A4 envelope for your equipment.

How the result changes with Racks per row

Racks per rowTotal racks
1144
36144
65260
90360

What each input means

Racks per row
Number of rack cabinets in each row.
Number of rows
Total rows of racks (pairs face each other across cold aisles).
Avg power per rack (kW)
Average IT power draw per rack. Low: 3-5kW, Medium: 7-10kW, High: 15-30kW.
Rack width (inches)
Rack cabinet width. Standard 19" rack is typically 24" wide with frame.
Cold aisle width (ft)
Width of cold (intake) aisles. ASHRAE recommends minimum 4ft.
Hot aisle width (ft)
Width of hot (exhaust) aisles. Can be narrower than cold aisles.
Supply air temp (°F)
Chilled supply air temperature entering cold aisles. ASHRAE A1: 64-80°F.

What each result means

Total racks
Total number of rack positions in the layout.
Total IT load (kW)
Combined IT power draw of all racks.
Required airflow (CFM)
Total cubic feet per minute of conditioned air needed.
Floor area (ft²)
Total raised floor area including racks and aisles.
Cold aisle velocity (FPM)
Air velocity in cold aisle. Target: <500 FPM for good containment.
Return air temp (°F)
Estimated hot aisle return air temperature.
Power density (W/ft²)
IT power per square foot of total floor area.
Containment efficiency (%)
Estimated cooling efficiency with containment at this velocity.

How this is calculated

Worked example, using the default values

  1. Identify Input Parameters
    4 parameters
    Racks per row = 10, Number of rows = 4, Avg power per rack (kW) = 7, Rack width (inches) = 24 = 7 input(s) provided
  2. Calculate Total racks
    Total racks
    40 = 40
  3. Calculate Total IT load
    Total IT load = totalRacks * avgPowerPerRackKw
    280 = 280
  4. Calculate Required airflow
    Required airflow = cfmPerRack * totalRacks
    35385 = 35385