Skip to main content
Calcimator

Water Infiltration Testing Calculator

Test procedure from wall type and ASTM standard.

Inputs

Results

Test pressure (PSF)

25

Test pressure (Pa)1,197
Water per test (gallons)50
Total water needed (gallons)250
Total test time (hours)4.6
Spray rack sections2
Estimated testing cost ($)$1,729.00
Test Pressures0, 12.5, 25
Spray DescriptionAAMA 501.2 spray rack
Pump Required0
Nozzles Needed0
How to Use This Calculator
  1. Enter Wall Area per Test (sq ft) — the area of each window, door, or curtain wall assembly being tested.
  2. Set Number of Test Locations based on ASTM requirements: include representative and worst-case conditions.
  3. Input Building Height (ft) — taller buildings experience higher wind-driven rain pressures on upper floors.
  4. Select Test Method (1=ASTM E1105, 2=AAMA 501.2 spray rack, 3=AAMA 502 hose nozzle).
  5. Choose Wind Zone (1=low to 4=hurricane) to set the design test pressure per local building code.
  6. Review Test Pressure (PSF), Water per Test (gallons), Total Test Time (hrs), and Estimated Testing Cost for project planning.

What each input means

Wall area per test (sq ft)
Area of wall covered by each test location (typically one window/door assembly).
Number of test locations
Total test locations. ASTM requires testing at representative and worst-case locations.
Building height (ft)
Total building height. Higher floors experience greater wind pressure.
Method (1=E1105, 2=501.2, 3=502)
1 = ASTM E1105 (pressure chamber). 2 = AAMA 501.2 (spray rack, most common). 3 = AAMA 502 (hose nozzle, quick check).
Wind zone (1=low to 4=hurricane)
1 = Low (90 mph). 2 = Moderate (110 mph). 3 = High (130 mph). 4 = Hurricane (150+ mph).
Test duration (minutes)
Duration of water spray per pressure stage. Standard is 15 minutes.

What each result means

Test pressure (PSF)
Design wind pressure for testing based on wind zone.
Test pressure (Pa)
Test pressure in Pascals for international reference.
Water per test (gallons)
Water consumption per test location per test cycle.
Total water needed (gallons)
Total water required for all test locations.
Total test time (hours)
Total time including setup, testing, and observation for all locations.
Spray rack sections
Number of spray rack sections needed (E1105/501.2 methods only).
Estimated testing cost ($)
Labor (2 technicians), equipment rental, and report preparation.

How this is calculated

Worked example, using the default values

  1. Identify Input Parameters
    4 parameters
    Wall area per test (sq ft) = 40, Number of test locations = 5, Building height (ft) = 60, Method (1=E1105, 2=501.2, 3=502) = 2 = 6 input(s) provided
  2. Calculate Test pressure
    25 = 25
  3. Calculate Test pressure
    Test pressure = designPressure * 47.88
    1197 = 1197
  4. Calculate Water per test
    Water per test = sprayRateGalPerHrPerSqFt * wallAreaPerTest * (testDurationMin / 60)
    50 = 50

Engine last updated . Checked against 2 independently-derived tests how we verify calculators.

The questions that sit next to this one — chosen by subject, including calculators filed under a different category.

More in Construction & Building Trades.