Skip to main content
Calcimator

Ground Loop Sizing Calculator

Calculate bore depth and loop length for a geothermal heat pump.

About this calculator

Sizing a geothermal ground loop starts with figuring out how much heat the ground actually has to absorb or reject, which is not the same as your building's heating or cooling load — the heat pump's coefficient of performance (COP) changes that number. In heating mode the ground only needs to supply the load minus the "free" compressor work, so ground extraction is heatingLoad × (1 − 1/COP); in cooling mode the ground has to reject the load plus that same compressor work, so ground rejection is coolingLoad × (1 + 1/COP) — cooling always demands more of the ground than heating does for an equivalent load. The calculator sizes the loop for whichever of those two dominates.

From there it applies rule-of-thumb footage-per-ton figures (175 ft/ton for vertical bores, 500 ft/ton for horizontal trenches) adjusted by two factors: soil conductivity (poor conductors like dry sand need proportionally more pipe than good conductors like wet clay) and a ground-temperature factor that rewards warmer ground in heating-dominant climates and cooler ground in cooling-dominant ones, clamped between 0.7x and 1.5x so extreme inputs don't produce absurd loop lengths. Vertical bores are then divided into 200 ft segments and horizontal loops into 200 ft trench runs to get a bore/loop count, and total pipe length doubles the bore depth to account for the U-tube's down-and-back path. This is a preliminary sizing tool built on national footage-per-ton averages, and it stops well short of a licensed engineer's formal loop design — actual installers use borehole thermal response testing and software like GLHEPro to account for soil variability, groundwater flow, and long-term thermal drift that a simple per-ton multiplier can't capture.

Inputs

BTU/hr
BTU/hr
°F
BTU/(hr·ft·°F)

Results

Total Bore/Trench Length

700 ft

≈ 9 tennis courts

Number of Bores/Loops

4

Total Loop Pipe1,400 ft
System Size4 tons
Ground Heat Exchange45,000 BTU/hr
How to Use This Calculator
  1. Enter the building's peak heating load and peak cooling load in BTU/hr.
  2. Enter the undisturbed ground temperature in °F.
  3. Set the heat pump's coefficient of performance (COP).
  4. Set the ground thermal conductivity for your soil type.
  5. Select the loop type: vertical bore or horizontal trench.
  6. Review the total bore/trench length, number of bores or loops, total loop pipe length, system size in tons, and ground heat exchange rate.

How the result changes with Ground Temperature

Ground TemperatureTotal Bore/Trench LengthNumber of Bores/Loops
40963 ft5
41939 ft5
80490 ft3

What each input means

Heating Load
Peak heating load in BTU per hour.
Cooling Load
Peak cooling load in BTU per hour.
Ground Temperature
Undisturbed ground temperature at depth.
Heat Pump COP
Coefficient of performance of the heat pump.
Soil Conductivity
Thermal conductivity of the soil. 0.5 dry sand, 1.0 average, 1.4 wet clay.
Loop Type
Ground loop installation type.

How this is calculated

Worked example, using the default values

  1. Identify Input Parameters
    4 parameters
    Heating Load = 48000, Cooling Load = 36000, Ground Temperature = 55, Heat Pump COP = 4 = 6 input(s) provided
  2. Calculate Total Bore/Trench Length
    Total Bore/Trench Length
    700 = 700
  3. Calculate Number of Bores/Loops
    4 = 4
  4. Calculate Total Loop Pipe
    Total Loop Pipe
    1400 = 1400
  5. Calculate System Size
    System Size
    4 = 4

Engine last updated . Checked against 3 independently-derived tests — how we verify calculators. Built by Paul Gunder, a software engineer, not a licensed financial, medical, or legal professional.

Frequently Asked Questions

Why does cooling mode require more ground heat exchange than heating mode for the same load?

In heating mode the ground only has to supply the load minus the "free" energy the compressor contributes, so ground extraction is heatingLoad × (1 − 1/COP). In cooling mode the ground has to absorb the load plus that same compressor work as rejected heat, so ground rejection is coolingLoad × (1 + 1/COP) — the plus sign instead of a minus sign is why cooling always demands more from the ground loop than an equivalent heating load.

How much difference does soil conductivity actually make to bore length?

The conductivity factor is simply 1 divided by your soil conductivity value, so it scales bore or trench length inversely — poor conductors like dry sand (around 0.5) roughly double the required footage compared to wet clay (around 1.4). Since this factor multiplies directly into the footage-per-ton figure for both vertical and horizontal loops, getting soil conductivity right matters as much as getting the load calculation right.

What does the ground-temperature factor do, and why is it clamped between 0.7 and 1.5?

For heating-dominant buildings, warmer ground than the 55°F reference shortens the required loop (since there's a smaller gap to bridge), while for cooling-dominant buildings, cooler ground shortens it instead — the calculator picks the right direction based on which load is larger. The clamp keeps unusually hot or cold ground-temperature inputs from producing an implausibly short or absurdly long loop length outside that 0.7x-1.5x range.

Why are vertical bores and horizontal trenches sized so differently in feet-per-ton?

Vertical bores use roughly 175 ft per ton because they reach deeper, more thermally stable ground, while horizontal trenches use about 500 ft per ton because they sit shallower where seasonal temperature swings and lower average conductivity mean each foot of pipe moves less heat. That's also why horizontal installations need much more total land even though each trench is typically cheaper to dig than a vertical borehole.

The questions that sit next to this one — chosen by subject, including calculators filed under a different category.

More in Energy & Utilities.