Cable Ampacity Calculator
Determine cable ampacity with NEC derating factors for temperature, conduit fill, and continuous loads.
Inputs
NEC 310.16: #14 AWG=15A; #12=20A; #10=30A; #8=50A; #6=65A (60°C THHN, 3 conductors)
NEC 310.4: THHN ampacity based on 75°C column for most terminations (NEC 110.14(C))
NEC base: 30°C; 40°C: derate to 0.87×; 50°C: 0.75×; 60°C: 0.58× of base ampacity
NEC 310.15(C)(1): ≤3 = 100%; 4–6 = 80%; 7–9 = 70%; 10–20 = 50%; 21–30 = 45%
NEC 210.19: continuous load conductor = 125% of load; breaker = 125% of continuous load
Results
Derated Ampacity
40 A
Required Breaker Size
40 A
How to Use This Calculator
- Select the Conductor Size in AWG — smaller AWG numbers indicate larger wires (e.g., AWG 10 is larger than AWG 14).
- Select the Insulation Type: THHN is the most common general-purpose wire; XHHW is used in wet locations.
- Enter the Ambient Temperature in °C around the conductors — NEC base is 30°C; higher temperatures require derating.
- Enter the number of Current-Carrying Conductors in the raceway — three or fewer requires no fill derating.
- Indicate whether this is a Continuous Load (3+ hours) — NEC requires conductors to be derated to 80% for continuous loads.
- Read the Derated Ampacity in amperes and the Required Breaker Size to confirm the circuit is properly protected.
How the result changes with Conductors in Raceway
| Conductors in Raceway | Derated Ampacity | Required Breaker Size |
|---|---|---|
| 4.9 | 32 A | 35 A |
| 15 | 20 A | 20 A |
| 26 | 18 A | 20 A |
| 36 | 18 A | 20 A |
What each input means
- Conductor Size (AWG)
- AWG wire size per NEC Table 310.12 (residential) or Table 310.16 (commercial/industrial). 14, 12, 10, 8, 6, 4, 3, 2, 1, 0 (for 1/0). Smaller number = larger wire.
- Insulation Type
- Conductor insulation type per NEC Article 310. THHN: 90°C dry/75°C wet, most common in conduit. XHHW: 90°C dry/75°C wet, better moisture resistance for wet locations.
- Ambient Temperature
- Ambient temperature around the conductors. NEC Table 310.16 base is 30°C (86°F). Apply correction factors from NEC Table 310.15(B)(1) for higher ambient temperatures.
- Conductors in Raceway
- Total current-carrying conductors in the raceway per NEC Table 310.15(C)(1). ≤3 conductors = no derating; 4–6 = 80%; 7–9 = 70%; 10–20 = 50%.
- Continuous Load?
- Select 1 if load operates for 3+ hours continuously. NEC 210.19(A)(1) and 215.2(A)(1) require conductors sized to 125% of continuous load (equivalent to 80% conductor loading).
How this is calculated
Worked example, using the default values
- Identify Input Parameters4 parametersConductor Size (AWG) = 10, Insulation Type = 1, Ambient Temperature = 30, Conductors in Raceway = 3 = 5 input(s) provided
- Calculate Derated AmpacityDerated Ampacity40 = 40
- Calculate Required Breaker SizeRequired Breaker Size40 = 40
- Calculate Base AmpacityBase Ampacity40 = 40
- Calculate Maximum Allowable LoadMaximum Allowable Load32 = 32
Related Calculators
The questions that sit next to this one — chosen by subject, including calculators filed under a different category.
Conduit Fill Calculator
Check NEC conduit fill compliance: calculate fill percentage, compare to code limits, and find maximum conductor count.
Electrical EngineeringVoltage Regulation Calculator
Calculate voltage drop, drop percentage, and receiving-end voltage for power cables with resistance and reactance.
Construction ElectricalFeeder Sizing Calculator
Feeder conductor size from load amps and distance, with voltage drop check per NEC 215.2.
Construction ElectricalData Cable Calculator
Cable runs, conduit fill per NEC Table 1, and pathway sizing from network drop count.
Data CenterCable Pathway Calculator
Cable tray and ladder capacity from cable count, diameter, and tray dimensions per NEC Article 392.
More in Engineering.