Skip to main content
Calcimator

Conduit Fill Calculator

Check NEC conduit fill compliance: calculate fill percentage, compare to code limits, and find maximum conductor count.

Inputs

mm

NEC Chapter 9: 1 conductor = 53% fill; 2 conductors = 31%; 3+ conductors = 40% max fill

AWG
conductors

NEC Table 1: 1 conductor = 53% fill; 2 = 31%; 3+ = 40% max of conduit inside area

(1=THHN, 2=XHHW)

THHN #12: 3.96 mm OD; XHHW #12: 4.50 mm OD per NEC Chapter 9 Table 5

Results

Fill Percentage

9.1%

NEC Compliant?

1 (1=yes, 0=no)

Conduit Internal Area387 mm²
Area per Conductor11.68 mm²
Total Fill Area35.04 mm²
Max Conductors Allowed13 conductors
How to Use This Calculator
  1. Select the Conduit Trade Size in mm: 16 mm = 1/2", 21 mm = 3/4", 27 mm = 1", 35 mm = 1-1/4", 53 mm = 2".
  2. Enter the Conductor Size in AWG and the Conductor Type (THHN or XHHW) — conductor OD varies by insulation type.
  3. Enter the Number of Conductors to be pulled through the conduit.
  4. Review the Fill Percentage — NEC Chapter 9 allows 40% fill for 3+ conductors, 31% for 2, and 53% for 1 conductor.
  5. Check the NEC Compliant? output — a value of 1 means the fill is within limits; 0 means you must upsize the conduit.
  6. Note the Max Conductors Allowed to quickly assess how many more wires could be added to an existing conduit.

How the result changes with Number of Conductors

Number of ConductorsFill PercentageNEC Compliant?
4.914.8%1 (1=yes, 0=no)
1545.3%0 (1=yes, 0=no)
2678.5%0 (1=yes, 0=no)
36108.7%0 (1=yes, 0=no)

What each input means

Conduit Trade Size
Conduit trade size per NEC Chapter 9 Tables. Common: 16 (1/2"), 21 (3/4"), 27 (1"), 35 (1-1/4"), 41 (1-1/2"), 53 (2"). Fill limits per NEC Table C1–C12 based on conduit type.
Conductor Size (AWG)
AWG wire size: 14, 12, 10, 8, 6, 4, 3, 2, 1, 0. Smaller number = larger wire.
Number of Conductors
Total number of conductors to be installed in the conduit. NEC Chapter 9 Table 1 limits fill to 40% for 3+ conductors to ensure proper heat dissipation and installation ease.
Conductor Type
Conductor insulation type per NEC Article 310. THHN and XHHW have different outer diameters per NEC Chapter 9 Table 5, which directly affects conduit fill calculations.

How this is calculated

Worked example, using the default values

  1. Identify Input Parameters
    4 parameters
    Conduit Trade Size = 27, Conductor Size (AWG) = 12, Number of Conductors = 3, Conductor Type = 1 = 4 input(s) provided
  2. Calculate Fill Percentage
    Fill Percentage
    9.1 = 9.1
  3. Calculate NEC Compliant?
    NEC Compliant?
    1 = 1
  4. Calculate Conduit Internal Area
    Conduit Internal Area
    387 = 387
  5. Calculate Area per Conductor
    11.68 = 11.68

The questions that sit next to this one — chosen by subject, including calculators filed under a different category.

More in Engineering.