Skip to main content
Calcimator

Compressed Air Quality Calculator

ISO 8573 air quality class from application requirements.

Inputs

%

Results

ISO 8573 Particle Class

5

ISO 8573 Water Class

4

ISO 8573 Oil Class

3

Required dew point (°F)37
Max oil content (mg/m³)1
Dryer type needed2
Filtration stages1
Est. condensate (gal/day)4.6
How to Use This Calculator
  1. Enter the application type to set ISO 8573-1 quality class requirements.
  2. Input current measured particulate count, pressure dew point, and oil content.
  3. Review which ISO class is achieved for each contaminant.
  4. Compare current quality to the required class for your most sensitive application.
  5. Use the output to specify the correct filtration, drying, and separation equipment.

What each input means

Application type
1 = General plant air, 2 = Spray painting, 3 = Food/beverage, 4 = Pharmaceutical, 5 = Electronics, 6 = Instrument air.
System flow rate (CFM)
Total compressed air flow rate for condensate estimation.
Ambient temperature (°F)
Ambient air temperature entering the compressor intake.
Ambient humidity (%)
Relative humidity of ambient air at the compressor intake.

What each result means

ISO 8573 Particle Class
Required particulate cleanliness class (1 = cleanest, 6 = least stringent).
ISO 8573 Water Class
Required moisture/dew point class (1 = driest, 6 = least stringent).
ISO 8573 Oil Class
Required oil content class (1 = cleanest, 4 = least stringent).
Required dew point (°F)
Pressure dew point the dryer must achieve for the water class.
Max oil content (mg/m³)
Maximum allowable total oil aerosol and vapor concentration.
Dryer type needed
1 = None/membrane, 2 = Refrigerated, 3 = Desiccant, 4 = Heated desiccant.
Filtration stages
Number of filtration stages recommended for the particle class.
Est. condensate (gal/day)
Estimated condensate generation requiring drainage and treatment.

How this is calculated

Worked example, using the default values

  1. Identify Input Parameters
    4 parameters
    Application type = 1, System flow rate (CFM) = 100, Ambient temperature (°F) = 85, Ambient humidity (%) = 60 = 4 input(s) provided
  2. Calculate ISO 8573 Particle Class
    ISO 8573 Particle Class
    5 = 5
  3. Calculate ISO 8573 Water Class
    ISO 8573 Water Class
    4 = 4
  4. Calculate ISO 8573 Oil Class
    ISO 8573 Oil Class
    3 = 3
  5. Calculate Required dew point
    Required dew point
    37 = 37
  6. Calculate Max oil content
    Max oil content
    1 = 1

The questions that sit next to this one — chosen by subject, including calculators filed under a different category.

More in Engineering.