Skip to main content
Calcimator

Dryer Selection Calculator

Refrigerated or desiccant dryer from dewpoint requirement.

About this calculator

Dryer selection is driven almost entirely by how dry your process needs the air to be. This calculator picks a technology from your required pressure dew point: 35°F and warmer routes to a refrigerated dryer with no purge air consumed; colder targets down to -40°F go to a membrane dryer if your flow is small (≤50 CFM) or otherwise a heatless desiccant dryer, both of which consume compressed air internally to regenerate their drying media (18% and 15% purge loss, respectively); and anything below -40°F calls for a heated desiccant dryer, which trades a lower purge loss (7%) for direct electrical heating. Once a type is chosen, the calculator applies two CAGI-style correction factors to the rated capacity: dryers are rated at a 100°F inlet, so hotter incoming air derates capacity by about 1.5% per degree above that baseline (and slightly uprates it below), and capacity is also corrected for operating pressure relative to a 100 psig baseline, since lower system pressure means the dryer must handle a larger actual air volume for the same mass flow.

The corrected capacity, minus whatever air the dryer consumes as purge, gives the net air actually delivered downstream. Power estimates differ sharply by type — a refrigerated dryer's own compressor draws roughly 0.2 kW per 100 CFM, while heatless and membrane dryers use minimal direct power but push their real cost onto the plant's air compressor, which has to generate the purge air; that indirect cost is folded into the "total system impact" figure using a rough 4.5 CFM-per-horsepower conversion. Because these are industry rule-of-thumb figures rather than a specific manufacturer's CAGI-certified data sheet, use the output to shortlist a dryer category and rough operating cost, then confirm against the vendor's actual performance curves.

Inputs

°F
°F

Results

Recommended dryer type

1

Required dryer capacity (CFM)

100

Purge air loss (%)0
Purge air (CFM)0
Net delivered air (CFM)100
Dryer power (kW)0.2
Total system impact (kW)0.2
Temperature correction1
How to Use This Calculator
  1. Enter the compressed air flow rate (CFM) the dryer must handle.
  2. Set the required pressure dew point for your application — 35°F selects a refrigerated dryer, colder targets select a desiccant or membrane dryer.
  3. Input the dryer inlet air temperature and system operating pressure.
  4. Review the recommended dryer type and the required dryer capacity (CFM) after temperature and pressure corrections.
  5. Check the purge air loss, net delivered air, and dryer power (kW) to estimate the operating cost of the recommended dryer.

How the result changes with Required dew point (°F)

Required dew point (°F)Recommended dryer typeRequired dryer capacity (CFM)
182100
262100
501100

What each input means

Air flow rate (CFM)
Compressed air flow rate the dryer must handle.
Required dew point (°F)
Target pressure dew point. 35°F = refrigerated dryer, -40°F = desiccant, -100°F = heated desiccant.
Dryer inlet temperature (°F)
Air temperature entering the dryer (after aftercooler). Higher temps require larger dryer capacity.
Operating pressure (psig)
System operating pressure. Lower pressure requires larger dryer capacity.

What each result means

Recommended dryer type
1 = Refrigerated, 2 = Heatless desiccant, 3 = Heated desiccant, 4 = Membrane.
Required dryer capacity (CFM)
Dryer nameplate capacity needed after temperature and pressure corrections.
Purge air loss (%)
Percentage of compressed air consumed by the dryer regeneration process.
Purge air (CFM)
Actual CFM of compressed air lost to dryer regeneration.
Net delivered air (CFM)
Usable air output after purge losses.
Dryer power (kW)
Direct electrical power consumed by the dryer unit.
Total system impact (kW)
Combined dryer power plus compressor energy for purge air.
Temperature correction
Capacity correction factor for inlet temperature (1.0 at 100°F).

How this is calculated

Worked example, using the default values

  1. Identify Input Parameters
    4 parameters
    Air flow rate (CFM) = 100, Required dew point (°F) = 35, Dryer inlet temperature (°F) = 100, Operating pressure (psig) = 100 = 4 input(s) provided
  2. Calculate Recommended dryer type
    1 = 1
  3. Calculate Required dryer capacity
    Required dryer capacity = flowRateCfm * tempCorrectionFactor * pressureCorrectionFactor
    100 = 100
  4. Calculate Purge air loss
    0 = 0
  5. Calculate Purge air
    Purge air = correctedCapacityCfm * (purgeAirPct / 100)
    0 = 0

Engine last updated . Checked against 4 independently-derived tests — how we verify calculators. Built by Paul Gunder, a software engineer, not a licensed financial, medical, or legal professional.

Frequently Asked Questions

Why did the calculator recommend a heatless desiccant dryer instead of a membrane dryer for my low dew point requirement?

Membrane dryers are only recommended for smaller flows — 50 CFM or less — because their 18% purge air consumption is proportionally more costly at higher flow rates. Above 50 CFM at the same dew point requirement, the calculator switches to a heatless desiccant dryer, which uses a slightly lower 15% purge but scales better to larger systems.

What's the difference between dryer power and total system impact?

Dryer power is only the electricity the dryer unit itself draws directly — minimal for heatless desiccant and membrane types, since they use compressed air rather than heaters to regenerate. Total system impact adds in the equivalent compressor power needed to generate that lost purge air, which is often the larger real cost for purge-based dryer types.

How much does inlet air temperature actually change the required dryer size?

Dryers are rated for a 100°F inlet, and capacity derates about 1.5% for every degree above that — so a dryer receiving 130°F air, a hot aftercooler discharge, needs roughly 45% more nameplate capacity than the same flow at 100°F to hit the same dew point. Cooler inlet air below 100°F gets a small capacity credit instead.

Why does lower operating pressure increase the required dryer capacity?

The pressure correction factor is based on the ratio of absolute pressures relative to a 100 psig baseline, since a fixed mass flow of air occupies a larger actual volume at lower pressure. Running the same CFM-rated flow at 80 psig instead of 100 psig requires a noticeably larger dryer to achieve the same dew point, because the dryer has to process a bigger actual air volume.

The questions that sit next to this one — chosen by subject, including calculators filed under a different category.

More in Engineering.