Kitchen Hood Suppression Calculator

Kitchen fire suppression system sizing from hood dimensions.

About this calculator

This calculator sizes a wet-chemical kitchen suppression system per NFPA 17A, the Standard for Wet Chemical Extinguishing Systems, and UL 300 listing requirements, by counting how many nozzles the hood, appliances, and duct actually need. Each fryer, grill/griddle section, and other heat-producing appliance you enter gets one dedicated nozzle, reflecting how these systems are actually listed — a fryer's nozzle aims into the vat, a grill's nozzle sweeps the cooking surface. The plenum adds one nozzle per 10 feet of hood length, and the duct adds one nozzle at the collar plus one more for every additional 20 feet of duct run.

Total nozzle count then drives the wet-chemical agent quantity at a rough 1.5 gallons per nozzle, which is matched up to the nearest standard tank size (1.5, 2.5, 3, 4, or 6 gallons); if demand exceeds a single 6-gallon tank, the calculator adds tanks rather than assuming one oversized vessel. It also flags the number of fuel/electric shutoff valves needed (one per appliance, since NFPA 17A requires the system to cut power/gas to protected appliances on discharge) and estimates portable Class K extinguishers required within 30 feet of travel distance per NFPA 10. The cost range is a rough order-of-magnitude estimate built from a base install cost plus a per-nozzle adder — actual quotes vary significantly by manufacturer, agent brand, and local labor rates, so use this for budgeting, not bidding.

Inputs

ft
ft
ft

Results

Total nozzles required

6

Appliance nozzles4
Plenum nozzles1
Duct nozzles1
Wet chemical agent (gal)9
Tank size (gal)6
Number of tanks2
Gas valve shutoffs4
K-class extinguishers needed1
Hood area (sq ft)40

Figures current as of 2026. Source: National Fire Protection Association, NFPA 17A, Standard for Wet Chemical Extinguishing Systems

How to Use This Calculator
  1. Enter Hood length (ft), Hood width (ft), and Number of deep-fat fryers.
  2. Set Number of grills/griddles, Other cooking appliances, and Duct length (ft).
  3. Review the Total nozzles required result.
  4. Use Appliance nozzles and Plenum nozzles to inform your decision.

How the result changes with Hood length (ft)

Hood length (ft)Total nozzles required
56
7.56
157
258

What each input means

Hood length (ft)
Length of the kitchen exhaust hood in feet.
Hood width (ft)
Width (depth) of the kitchen exhaust hood in feet.
Number of deep-fat fryers
Each fryer requires a dedicated suppression nozzle per UL 300 listing.
Number of grills/griddles
Flat grills and griddles each require nozzle coverage.
Other cooking appliances
Ranges, woks, broilers, and other heat-producing appliances.
Duct length (ft)
Length of exhaust duct from hood collar to exterior termination.

What each result means

Total nozzles required
Sum of appliance, plenum, and duct nozzles.
Appliance nozzles
Nozzles aimed at cooking surfaces.
Plenum nozzles
Nozzles protecting the hood plenum area.
Duct nozzles
Nozzles for exhaust duct protection.
Wet chemical agent (gal)
Estimated agent quantity at ~1.5 gal per nozzle.
Tank size (gal)
Recommended standard tank size.
Number of tanks
Tanks required (multiple if demand exceeds 6-gal single tank).
Gas valve shutoffs
Fuel/electric shutoff actuators required for appliances.
K-class extinguishers needed
Portable K-class extinguishers required within 30 ft travel per NFPA 10.
Hood area (sq ft)
Calculated hood coverage area.

How this is calculated

Worked example, using the default values

  1. Identify Input Parameters
    4 parameters
    Hood length (ft) = 10, Hood width (ft) = 4, Number of deep-fat fryers = 2, Number of grills/griddles = 1 = 6 input(s) provided
  2. Calculate Total nozzles required
    Total nozzles required
    6 = 6
  3. Calculate Appliance nozzles
    Appliance nozzles
    4 = 4
  4. Calculate Plenum nozzles
    Plenum nozzles
    1 = 1

Figures and sources

Engine last updated . Checked against 3 independently-derived tests — how we verify calculators. Built by Paul Gunder, a software engineer, not a licensed financial, medical, or legal professional.

Frequently Asked Questions

Why does each fryer get its own nozzle while the duct only gets one nozzle every 20 feet?

Appliance nozzles are aimed directly at a cooking surface — a fryer's nozzle discharges into the vat, a grill's sweeps the cooking area — so the calculator counts one per fryer, grill/griddle section, and other appliance you enter, since UL 300 listings require dedicated coverage per appliance. The duct, by contrast, is a long enclosed volume rather than a hazard source, so it only needs a nozzle at the collar plus one more for every additional 20 feet of run to keep grease fire from spreading through the ductwork.

How does the calculator pick a tank size, and what happens if my nozzle count needs more agent than the biggest tank holds?

It multiplies your total nozzle count by roughly 1.5 gallons of wet chemical agent per nozzle, then matches that against the smallest standard tank size (1.5, 2.5, 3, 4, or 6 gallons) that can hold it. If the required agent volume exceeds even a single 6-gallon tank, the calculator switches to reporting multiple tanks (agent gallons divided by 6, rounded up) rather than assuming one oversized vessel exists.

Why do I need portable K-class extinguishers if the hood already has a suppression system?

The built-in wet-chemical system protects the hood, plenum, and appliances automatically, but NFPA 10 separately requires portable Class K extinguishers within 30 feet of travel distance for staff to fight a residual or reignited grease fire by hand. The calculator estimates this count from hood length divided by 30 feet, with a minimum of one extinguisher regardless of how short the hood is.

What's actually included in the cost estimate range, and why is it so wide?

The low end is $3,000 base plus $500 per nozzle, and the high end is $6,000 base plus $1,000 per nozzle — a deliberately wide band meant to capture the spread between a basic single-manufacturer install and a more complex job with premium components or difficult access. It doesn't itemize labor rates, permit fees, or regional pricing differences, so treat it as an order-of-magnitude budgeting figure rather than a quote.